Siemens TX-I/O Engineering and installation guide CM110562en_13
Building Technologies Principles of electrical design 2019-05-15
10.6.7 Installation examples for island bus expansion
In the installation examples, the island bus length is the same on both side of
the island bus expansion (1/2 Lmax). Concerning Lmax, please refer to page 81.
Permissible power changes when other lengths are selected (see rule 21).
< 200 m
< 1/2 Lmax
< 1.2A
P
10562z154
< 1.2A
< 1/2 Lmax
Q
< 1/2 Lmax
< 1.2A
< 1.2A
< 1/2 Lmax
< 1.2A
< 1/2 Lmax
< 1.2A
< 1/2 Lmax
< 200 m< 200 m< 200 m
< 200 m
Example P illustrates (versus example A) that power can be doubled thanks cutting
the length of the island bus in half (1/2 Lmax, Rule 21 / 22, page 92)
(1.2A instead of 0.6 A in the remote I/O row).
Example Q illustrates
(versus example P), for each sub-island, the island bus length "1/2 Lmax" is once
again allowed.
the length of the island bus expansion segment (max. 200 m) can be distributed
as desired on decentralized sub-islands (in extreme cases 198 + 1 + 1 m,
1 + 198 m + 1 or 1 + 1 + 198 m).