Siemens Desigo Room automation - Engineering, mounting and installation CM111043en_14
Smart Infrastructure Electrical features of inputs & outputs 2020-10-30
8.2.3 Technical data for the analog inputs
Compensation of the line
resistance
1 Ohm, calibrated in the module,
(except for NTC3K, NTC10K, and NTC100K)
TX
-
I/O
DXR2
Signal type Range
(Under / over
range)
3)
Resolution Range
(Under / over range)
3)
Resolution
Resistance AI 1000 Ohm 0...2500 Ohm
(0...2650 Ohm)
100 mOhm 0...1000 Ohm
(0...1050 Ohm)
1 Ohm
Resistance AI 2500 Ohm 0...2500 Ohm
(0...2650 Ohm)
100 mOhm 0...2500 Ohm
(0...2625 Ohm)
2.5 Ohm
Resistance AI 10 kOhm 0...10 kOhm
(0...10.5 kOhm)
10 Ohm
Resistance AI 100 kOhm 0...100 kOhm
(0...105 kOhm)
100 Ohm
Temperature AI PT1K 375
-50…150 °C
(-52.5 ...185.0 °C)
10 mK
0.018 °F
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
25 mK
0.045 °F
Temperature AI PT1K 385
-50...400 °C
(-52.5...610°C)
20 mK
0.036 °F
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
25 mK
0.045 °F
Temperature AI Ni1000
LG-Ni 1000)
-50...150°C
(-52.5...155.0 °C)
10 mK
0.018 °F
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
25 mK
0.045 °F
Temperature AI Ni1000 DIN -40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
25 mK
0.045 °F
Temperature AI T1 (PTC)
-50...130 °C
(-52.5...155.0 °C)
10 mK
0.018 °F
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
100 mK
0.18 °F
Temperature AI NTC 3K -40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
25 mK (25 °C)
0.045 °F (77 °F)
Temperature AI NTC 10K
-40...115 °C
1)
(-52.5...155°C)
10 mK
0.018 °F
(25°C)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
25 mK (25 °C)
0.045 °F (77 °F)
Temperature AI NTC 100K
-40 ...125 °C
1)
(-52.5...155°C)
10 mK
0.018 °F
(25°C)
-10...70 °C (-15...75 °C)
14...158 °F (5...167 °F)
25 mK (25 °C)
0.045 °F (77 °F)
Voltage measuring
AI 0-10V
2)
0 ... 10 V
2)
(-1.5...11.5 V)
1 mV 0 ... 10 V
2)
(-1.0...11.0 V)
2 mV
Voltage measuring
AI 0-10V norm
2)
0...100%
(-10...110%)
2 mV
1)
Only with reduced hum injection (details see 7.1.2)
2)
Range monitoring of signal type AI 0-10V:
TX-I/O: short NEGATIVE signal –3.1 V (open circuit), 0.05 mA (shorted)
– DXR: permanently -1.5 V, 0.008 mA.
If a field device has no power supply, the negative voltage can damage any
polarized components (e.g. capacitors) in the field device.
3)
When the process value is outside the range, a fault message is issued.
Caution!