Siemens Desigo Room automation - Engineering, mounting and installation CM111043en_13
Smart Infrastrructure Installation box / panel for TRA 2020-04-30
5 Installation box / panel for TRA
5.1 Requirements
Please read Sections 5.1 "Panel requirements" and 5.3 "EMC compliant panel" in
the TX-I/O engineering and installation guide [8] prior to engineering and executing
the installation box.
Observer the following for mounting and installation.
– Installation depth
– Maintain sufficient cable distance to be able to easily snap on and remove the
screw terminal blocks, even if the automation stations are mounted.
– Room automation stations can be mounted directly next to one another; a
distance of ca. 2 cm is recommended, however, for facilitate access.
– Reserve sufficient free space for subsequent extensions.
The room automation stations and TX-I/O modules are designed for installation on
standard rails (prerequisite to establishing the island bus connection using TX-I/O
modules).
Permissible standard rails:
· Top hat rails TH35-7.5 as per EN60715 (35 x 7.5 mm).
· Other top hat rails that meet the following conditions:
– Material thickness exterior max. 1 mm, min. 3 mm in depth
– Internal opening at least 25 mm.
min. 25
35
35
10762M044
(25)
35 ± 0,3
27 ±
0,2
1 ± 0.04
7.5
-0.4
0
1 ± 0.04
min. 3
min. 6.5
min. 25
min. 6.5
The room automation station may also be attached to a wall if used without TX-I/O
modules.
Systems with TX-I/O
modu
l
es
Space requirements
Installation mode
Standard rails
Wall mounting