8.2.2 Active sensors DC 0 … 10 V
The active sensors use a signal amplifier which emits a standard DC 0...10 V
signal. This voltage range is proportional to the application range of the sensor.
Active sensors are available for:
Relative humidity
Pressure in liquid and gaseous media
Differential pressure in liquid and gaseous media
Air quality
Air velocity
1076 2d037_01
0 %
U
x
100 %
0 V
10 V
Key
U Sensor signal (voltage)
x Measured value
(0…100% = application range)
When the process value is outside -1.5...11.5 V, a fault message will be sent.
For a workaround (Zener diode), see CM110563.
Measured value
acquisition and
measured signal