Data Sheet for Product
OpenAir™ Non-Spring Return, 24 Vac, Floating Control, Rotary, Electric Damper Actuator  Technical Instructions 
  Document No. 155-188P25 
  May 22, 2014 
Siemens Industry, Inc.  Page 7 
Mounting and 
Installation 
You must place the actuator on the damper shaft so that the front of the actuator is 
accessible. The label is on the front side. 
The minimum damper drive shaft length is 3/4-inch (20 mm).  
1/2-inch Ø Guide 
Factory Installed 
3/8-inch Ø 
Use shaft insert supplied 
for any 3/8-in (8 - 10 mm) 
diameter shaft 
5/8-inch Ø 
NOTE:  For all damper shafts with the exception of the 1/2-inch round shaft: 
Remove 1/2-inch Ø guide before installation. 
Figure 15. Damper Shaft Sizes. 
•  A mounting bracket is included with the actuator.  
•  Observe the service envelope around the actuator as shown in 
XFigure 25X. 
•  Detailed mounting instructions are included with each actuator. 
Manual override 
To move the damper blades and lock the 
position with no power present: 
1.  Slide the red manual override knob 
toward the back of the actuator. 
2.  Make adjustments to the damper 
position. 
3.  Slide the red manual override knob 
toward the front of the actuator. 
Once power is restored, the actuator returns 
to automated control
. 
Figure 16. Manual Override. 
Mechanical range 
adjustment 
1.  Loosen the stop set 
screw. 
2.  Move the screw along 
the track to the desired 
position, and fasten it in 
place.  
Figure 17. Moving the Mechanical Range Stop. 
1
2