Data Sheet for Product

Technical Instructions 599 Series 3-Way Ball Valves
Document Number 155-201
May 28, 2020
Page 4 Siemens Industry, Inc.
Use Table 3 to determine the effective Cv when using a full-port ball valve where the ball size and the lines size differ.
Table 3. Full-Port (No Flow Optimizer) 3-Way Ball Valve Product Numbers and Flow Coefficients.
Valve
Line
Size in
Inches
(mm)
Valve
Product
Number
Effective (Installed) Cv (Kvs)
Supply Line Size in Inches (mm)
1/2
(13)
3/4
(20)
1
(25)
1-1/4
(32)
1-1/2
(38)
2
(51)
2-1/2
(63)
3
(76)
4
(102)
5
(127)
6
(152)
1/2
(15)
599-10357(S)
10.00
(8.62)
6.94
(5.93)
6.19
(5.29)
--
--
--
--
--
--
--
--
3/4
(20)
599-10360(S)
--
16.00
(13.79)
13.9
(11.98)
12.4
(10.69)
--
--
--
--
--
--
--
1
(25)
599-10363(S)
--
--
25.00
(21.55)
22.5
(19.40)
21.2
(18.27)
--
--
--
--
--
--
1-1/4
(32)
599-10366(S)
--
--
--
40.00
(34.48)
36.9
(31.81)
33.3
(28.70)
--
--
--
--
--
1-1/2
(40)
599-10369(S)
--
--
--
--
63.00
(54.31)
55.3
(47.67)
51.00
(43.96)
--
--
--
--
2
(50)
599-10372(S)
--
--
--
--
--
100
(86.21)
94.3
(81.29)
86.1
(74.23)
--
--
--
= Valve may be oversized.
= Optimal valve size.
= Valve may be undersized.
Application
Ball valves can control hot or chilled water and up to 50% glycol solution in mixing
applications for air handlers, convectors, fan coil units, unit conditioners, radiation, and
reheat coils. Three-way ball valves can be piped for either mixing or diverting
applications. See Figure 1 and Figure 2 for piping configurations for mixing and
diverting applications, respectively.
Figure 1. Mixing Application. Figure 2. Three-way Diverting Application.