NOTE: Use Table 11 to determine the effective Cv when using a full-port ball valve where the ball size and the
line sizes differ.
Table 11. Full-Port (No Flow Characterizer) Ball Valve Product Numbers and Flow Coefficients.
Valve
Line Size
in
Inches
(mm)
Valve
Product
Number
Effective (Installed) Cv (Kvs)
Supply Line Size in Inches (mm)
1/2
(13)
3/4
(20)
1
(25)
1-1/4
(32)
1-1/2
(38)
2
(51)
2-1/2
(63)
3
(76)
4
(102)
5
(127)
6
(152)
1/2 (15)
599-10307
599-10307S
10.00
(8.62)
6.94
(5.93)
6.19
(5.29)
3/4 (20)
599-10311
599-10311S
25.00
(21.55)
18.66
(15.95)
15.35
(13.12)
1 (25)
599-10316
599-10316S
63.00
(54.31)
39.78
(34.00)
33.56
(28.69)
1-1/4 (32)
599-10321
599-10321S
100.00
(86.21)
69.19
(59.13)
51.45
(43.98)
1-1/2 (40)
599-10324
599-10324S
63.00
(54.31)
55.34
(47.30)
51.00
(43.59)
599-10326
599-10326S
160.00
(137.93)
93.80
(80.17)
76.34
(65.25)
2 (50)
599-10329
599-10329S
100.00
(86.21)
94.30
(80.60)
86.12
(73.61)
= Valve may be oversized.
= Optimal valve size.
= Valve may be undersized.
Operation
The parabolic shape of the flow characterizer orifice (Figure 2) provides a slowly
opening valve. Equal movements of the valve stem, at any point of the flow range,
change the existing flow an equal percentage regardless of the existing flow. The ball
valve equal percentage flow characteristic (Figure 3) mirrors the flow characteristic of a
coil, resulting in linear heat transfer.
Figure 2. Ball Valve Flow
Characterizer.
Figure 3. Ball Valve Equal Percentage
Flow Control.