TH 192 DN Day-Night and DNV Day-Night-Vent Room Thermostat Technical Instruction
155-067P25
Rev. 1, July, 1999
Siemens Building Technologies, Inc. Page 11
Landis Division
Night Time Calibration
S
SS
St
tt
te
ee
ep
p p
p 1
11
1 —
If not already done, remove cover
using 192-632 calibration tool. Verify
room temperature is between 70 and
80
°
F (21 and 27
°
C).
S
SS
St
tt
te
ee
ep
p p
p 2
22
2 —
Verify that supply pressure is 25 psi (172 kPa).
Set night time dial to room temperature by
turning the exposed adjustment knob or using a
hex key as shown. Allow thermostat to stand for
about five minutes to adjust to the new setting.
S
SS
St
tt
te
ee
ep
p p
p 3
33
3 —
Moisten needle and insert 192-633
test gauge and needle adapter in the
test port. Read control pressure.
S
SS
St
tt
te
ee
ep
p p
p 4
44
4 —
If control pressure does not read 7 to 8 psi (48 to
55 kPa), turn calibration screw using 192-632
calibration tool or 1/8” (3.2 mm) wrench until
pressure is 7 to 8 psi (48 to 55 kPa). The sensing
element is now in calibration and the set point
can be changed to the desired room temperature.