Data Sheet for Product
TH 192 DN Day-Night and DNV Day-Night-Vent Room Thermostat Technical Instructions
Document Number 155-067P25
February 11, 2022
Siemens Industry, Inc. Page 5
Specifications
Control action See Table 2.
Operating ranges 45 to 85°F (7 to 30°C)
Supply air pressure, maximum 30 psi (207 kPa)
Normal air supply pressure
Day 18 psi (124 kPa)
Night 25 psi (172 kPa)
Sensitivity adjustment 1 to 4 psi/°F (12 to 50 kPa/°C)
Nominal air consumption, two-pipe 25 scim (6.8 ml/sec)
Temperature
Storage temperature -10 to 140°F (-23 to 60°C)
Ambient operating temperature 40 to 140°F (4 to 60°C)
Temperature response 0.1°F (0.06°C)
Dial graduations 2°F (1°C)
Factory settings
Calibration @ 72°F (22°C) 7.5 psi (52 kPa)
Sensitivity 2.5 psi/F (31 kPa/C)
Limit stop adjustment 45 and 85°F (7 and 30°C)
Standard cover Cycolac, desert beige
Shipping weight 0.7 lbs. (0.3 kg)
Dimensions See Figure 4.
Accessories
See the following Technical Bulletins for information on accessories.
Technical Bulletin
TB 237 Terminal Kits
TB 214 Adapter Kits
TB 193 Guard Kit
TB 241 Test Head Kit
TB 167 Restrictors
Document Number
155-244
155-231
155-222
155-255
155-213
Dimensions
Figure 4. TH 192 DN and DNV Dimensions in Inches (Millimeters).