Product Overview

Thermostats
www.usa.siemens.com/hvaccomponents
A-10
Cover Description Plastic Metal
Adjustment setpoint concealed 192-262 192-362
Indicator setpoint concealed
Chassis thermometer concealed
Adjustment setpoint concealed 192-264 192-364
Indicator setpoint concealed
Chassis thermometer exposed
Adjustment setpoint key 192-269 192-369
Indicator setpoint exposed
Chassis thermometer concealed
Use with 1/2" setpoint knob option
Adjustment setpoint key 192-270 192-370
Indicator setpoint exposed
Chassis thermometer exposed
Use with 1/2" setpoint knob option
Adjustment setpoint key (night)
exposed (day) 192-271 192-371
Indicator setpoint exposed
Chassis thermometer exposed
Scale; Range
Major (minor) Divisions ............................................ 45 to 85°F, 10(2)°F
(7 to 30°C, 5(1)°C)
Factory Calibration .............................................................72°F, 7.5 psig
(22°C, 31 kPa)
Sensitivity Adjustment Range .................1 to 4 psi/°F (12 to 50 kPa/°C)
Factory Setting .................................................... 2.5 psig/°F (31 kPa/°C)
Limit Stop
Field Adjustment Range .............................................. 45/85°F (7/30°C)
Fixed Limit Stop Range ............................................... 55/75°F (3/24°C)
Temperature
Storage ......................................................-10 to +140°F (-23 to +60°C)
Ambient Operating ........................................... 40 to 140°F (4 to 60°C)
Accuracy at Factory
Calibration ........................................................................ ±2°F (±1.1°C)
Response ........................................................................ 0.1°F (0.06°C)
Supply Air Pressure
Two Pressure
Day (recommended) .............................................. 18 psig (124 kPa)
Night (recommended) ............................................ 25 psig (172 kPa)
Vent-Day/Night ............................... 0 psig (0 kPa)/25 psig (172 kPa)
Two Pressure
Day (range) ....................................... 15 to 19 psig (103 to 131 kPa)
Night (range) ..................................... 23 to 30 psig (159 to 207 kPa)
Two Pressure (Honeywell Competitive Model)
Day/Night .................................... 13 psig (90 kPa)/18 psig (124 kPa)
Two Pressure (Johnson Controls Competitive Model)
Day/Night .................................. 15 psig (103 kPa)/20 psig (138 kPa)
Nominal Air Consumption for
Air Compressor Sizing ................................................ 25 scim (6.8 ml/s)
Nominal Air Capacity for Air Main Sizing ................... 40 scim (11 ml/s)
Nominal Chassis Air Capacity
Supply ....................................................................... 230 scim (63 ml/s)
Exhaust ..................................................................... 150 scim (41 ml/s)
Air Connections .................................................... 5/32" (4 mm) OD tube
Dimensions (with cover)
192 DN ....................................................... 2.16" W x 3.34" H x 1.59" D
(55 mm W x 85 mm H x 40 mm D)
192 DNV ....................................................... 2.5" W x 3.34" H x 1.59" D
(64 mm W x 85 mm H x 40 mm D)
Shipping Weights
Thermostat Chassis and Wall Plate ............................ 0.53 lb. (0.24 kg)
Plastic Cover .............................................................. 0.07 lb. (0.04 kg)
Metal Cover (dual) ....................................................... 0.27 lb. (0.12 kg)
Thermostat Chassis
Model # Thermostat Chassis Type & Wall Plate
Air Output Thermometer &
Output Setpoint Capacity Setpoint Scales Control Action
D (DA)/ D (RA)/ D(DA)/
N (DA) N (RA) N (DA)
(with Night Vent)
°F 192-204 192-205 192-206
°C 192-224 192-225 192-226
Ordering Notes
DNV 3-pipe model provides full air supply on R2 vent port during night control cycle.
“Exposed features” are indicated in green on corresponding illustration.
For 194 refer to Powerstar Retroline section.
192 DN
192 DNV
3-pipe
Thermostat Covers
Sold Separately
For complete conversion kits, refer to the
Retroline
®
Retrostats starting on page A-15.
192 DN/DNVThermostat Covers
Code Color (add suf x to Part No.)
None Desert Beige (standard)
W White
Cover Color Options
PLASTIC COLORS
Code Description (add suf x to Part No.)
K Chassis with 1/2" (13 mm)
diameter setpoint adjustment
knob for convalescent facilities.
Chassis Options
Dual
(Day and Night)
High
(Integral Relay)
Single
Cover Description Plastic Metal
Specifi cations/Product Ordering