Product Overview
Thermostats
www.usa.siemens.com/hvaccomponents
A-10
Cover Description Plastic Metal
• Adjustment setpoint concealed 192-262 192-362
• Indicator setpoint concealed
• Chassis thermometer concealed
• Adjustment setpoint concealed 192-264 192-364
• Indicator setpoint concealed
• Chassis thermometer exposed
• Adjustment setpoint key 192-269 192-369
• Indicator setpoint exposed
• Chassis thermometer concealed
• Use with 1/2" setpoint knob option
• Adjustment setpoint key 192-270 192-370
• Indicator setpoint exposed
• Chassis thermometer exposed
• Use with 1/2" setpoint knob option
• Adjustment setpoint key (night)
exposed (day) 192-271 192-371
• Indicator setpoint exposed
• Chassis thermometer exposed
Scale; Range
Major (minor) Divisions ............................................ 45 to 85°F, 10(2)°F
(7 to 30°C, 5(1)°C)
Factory Calibration .............................................................72°F, 7.5 psig
(22°C, 31 kPa)
Sensitivity Adjustment Range .................1 to 4 psi/°F (12 to 50 kPa/°C)
Factory Setting .................................................... 2.5 psig/°F (31 kPa/°C)
Limit Stop
Field Adjustment Range .............................................. 45/85°F (7/30°C)
Fixed Limit Stop Range ............................................... 55/75°F (3/24°C)
Temperature
Storage ......................................................-10 to +140°F (-23 to +60°C)
Ambient Operating ........................................... 40 to 140°F (4 to 60°C)
Accuracy at Factory
Calibration ........................................................................ ±2°F (±1.1°C)
Response ........................................................................ 0.1°F (0.06°C)
Supply Air Pressure
Two Pressure
Day (recommended) .............................................. 18 psig (124 kPa)
Night (recommended) ............................................ 25 psig (172 kPa)
Vent-Day/Night ............................... 0 psig (0 kPa)/25 psig (172 kPa)
Two Pressure
Day (range) ....................................... 15 to 19 psig (103 to 131 kPa)
Night (range) ..................................... 23 to 30 psig (159 to 207 kPa)
Two Pressure (Honeywell Competitive Model)
Day/Night .................................... 13 psig (90 kPa)/18 psig (124 kPa)
Two Pressure (Johnson Controls Competitive Model)
Day/Night .................................. 15 psig (103 kPa)/20 psig (138 kPa)
Nominal Air Consumption for
Air Compressor Sizing ................................................ 25 scim (6.8 ml/s)
Nominal Air Capacity for Air Main Sizing ................... 40 scim (11 ml/s)
Nominal Chassis Air Capacity
Supply ....................................................................... 230 scim (63 ml/s)
Exhaust ..................................................................... 150 scim (41 ml/s)
Air Connections .................................................... 5/32" (4 mm) OD tube
Dimensions (with cover)
192 DN ....................................................... 2.16" W x 3.34" H x 1.59" D
(55 mm W x 85 mm H x 40 mm D)
192 DNV ....................................................... 2.5" W x 3.34" H x 1.59" D
(64 mm W x 85 mm H x 40 mm D)
Shipping Weights
Thermostat Chassis and Wall Plate ............................ 0.53 lb. (0.24 kg)
Plastic Cover .............................................................. 0.07 lb. (0.04 kg)
Metal Cover (dual) ....................................................... 0.27 lb. (0.12 kg)
Thermostat Chassis
Model # Thermostat Chassis Type & Wall Plate
Air Output Thermometer &
Output Setpoint Capacity Setpoint Scales Control Action
D (DA)/ D (RA)/ D(DA)/
N (DA) N (RA) N (DA)
(with Night Vent)
°F 192-204 192-205 192-206
°C 192-224 192-225 192-226
Ordering Notes
• DNV 3-pipe model provides full air supply on R2 vent port during night control cycle.
• “Exposed features” are indicated in green on corresponding illustration.
• For 194 refer to Powerstar Retroline section.
192 DN
192 DNV
3-pipe
Thermostat Covers
Sold Separately
For complete conversion kits, refer to the
Retroline
®
Retrostats starting on page A-15.
192 DN/DNVThermostat Covers
Code Color (add suffi x to Part No.)
None Desert Beige (standard)
W White
Cover Color Options
PLASTIC COLORS
Code Description (add suffi x to Part No.)
K Chassis with 1/2" (13 mm)
diameter setpoint adjustment
knob for convalescent facilities.
Chassis Options
Dual
(Day and Night)
High
(Integral Relay)
Single
Cover Description Plastic Metal
Specifi cations/Product Ordering