Product Overview

www.usa.siemens.com/hvaccomponents
Thermostats
A-9
Typical wall plate and screws.
192 DN Thermostat chassis.
192 DN Thermostat with plastic cover. Chassis wall plate
with easy maintenance plug-in adapters shown (optional).
Applications
The 192 DN and DNV Powerstar Pneumatic Room
Thermostat controls valves and damper actuators in
cooling equipment, automatically performing setback
changes from day to night. The 192 DNV also performs
a purge sequence at night to bring in “vent” outside air to
cool the building. A manual override selector switch allows
individual room or zone “day” control locally during the
night cycle.
During the night control cycle, the 192 DNV models
provide a separate output signal (full air supply) allowing
ventilation control. Periodic resetting to the “night” control
mode during evening or weekend periods using time
clocks ensures optimal energy management.
Recommendation
Use 192 DN or DNV for multiple valves and actuators, with
or without high/low limiting controls.
Description
Providing proportional dual setpoint, 2-pipe or 3-pipe high
air capacity pneumatic room temperature control, the
192 DN or DNV Powerstar Pneumatic Room Thermostat
automatically resets the room temperature setpoint during
unoccupied hours by changing the air pressure to the
thermostat. A manual override feature allows occupants
to switch to day mode. The override returns to night mode
the following night.
Features
Dual setpoint dial available in Fahrenheit or
Celsius scales
Available in direct or reverse acting models
Sensitive bimetal responds to temperature changes
Manual override selector for off-hour occupant comfort
Adjustable changeover pressure
Large volume air capacity relay
• Integral, eld adjustable limit stops
Wall mounting plate for connection to a variety of
rough-in terminal boxes included
Test port for fast check of output pressure without
removing the cover
Field replaceable thermometer, setpoint dial, restrictor
and lters
Options
Fixed limit stops to meet government speci cations
Quick-connect air connections for ease of installation
and service
Large, 1/2" setpoint knob for convalescent homes
Application Drawings
Chassis Port Operation Mode Switching Relay
R2 Pressure (Air Supply) Connection
Full Air Supply Night (S=25 psig) A-D
0 psig Night Occupied B-D
0 psig Day (S=18 psig) B-D
Day/Night.
Day/Night/Vent.
Powerstar Day/Night/Vent
Pneumatic Room Thermostats
192 DN/DNV