356 Limitem™ Rigid Bulb Thermostats
Features
Durable copper motor tube and 18” (457mm)
steel rod temperature sensing element.
Two-valve design reduces air waste.
Direct or reverse acting models.
Duct mount hardware included.
Rugged, all metal construction.
Applications
The 356 Limitem™ Rigid Bulb Thermostat provides
primary control for unit ventilators, fan coils and
other air handling units. This device can also be
used as low limit control for air flow to a controlled space.
Available in three temperature operating ranges:
0 to 100 °F (-18 to +38°C)
30 to 180°F (-1 to +82°C)
100 to 250°F (38 to 121°C)
Click on this link for 356 Limitem Rigid Bulb Technical Instructions
357 D Limitem™ Remote Bulb Thermostats
Features
Direct acting operation only.
Remote or averaging bulbs for
flexibility in installation .
Liquid-filling sensing element
for rapid response to changes
in temperature.
Two-valve design reduces air
waste.
Adjustable sensitivity.
Applications
The 357 D Limitem Remote Bulb Thermostat provides primary
monitoring and control for air handling units or a low limit control.
Available in three temperature operating ranges:
Averaging Bulb Model: 35 to 145°F (2 to 63°C)
Remote Bulb Model: 20 to 100°F (-7 to +38°C)
Remote Bulb Model: 120 to 230°F (48.9 to 110°C)
Click on this link for 357 D Limitem Remote Bulb Technical Instructions
188 Unit Mounted Thermostats
Features
Liquid-filled thermal system
temperature sensing element.
Durable die-cast metal case
with rugged setpoint knob.
Adjustable sensitivity.
Universal mounting bracket for
easy installation.
Integral adjustable limit stops.
Applications
The 188 Unit Mounted Thermostats are designed primarily for use in
fan coil induction units and unit ventilators to control the temperature
within an occupied space. The thermostat’s temperature range is
limited to applications at ambient temperatures.
Available with three control actions:
Direct Acting only (Heating)
Reverse Acting only (Cooling)
Heat or Cool depending on supply air pressure
Click on this link for 188 Unit Mount Thermostat Technical Instructions
134 Pneumatic High and Low
Temperature Detection Thermostats
Features
Snap-acting pneumatic switch.
Sight-set calibrated setpoint scale.
No leakage of air prior to reset of
switch
Easily adju.stable settings.
Normally closed air valve; bleeds to
less than 2 psi (14 kPa) when supplied
through a restrictor.
Applications
The 134 Pneumatic High and Low Temperature Detection Thermostats
are used on pneumatic heating and cooling systems in areas protected
from the weather.
On a typical high limit application, the thermostat shuts down air
conditioning or ventilating fans when the duct temperature becomes
excessively high. A normally closed switch opens at setpoint.
On a typical high limit application, the thermostat stops the fan or
closes a damper when the temperature drops to the setpoint at any
one foot (30.5 cm) or more of the sensing element.
Click on this link for 134 High-Low Temp Detect Technical Instructions