Thermostats
A-13
193 HC
Powerstar (Hesitation) Free Energy Band
Heating/Cooling Pneumatic Room Thermostats
Typical wall plate and screws.
193 HC Thermostat chassis.
193 HC Thermostat with plastic cover. Chassis wall plate
with easy maintenance plug-in adapters shown (optional).
Applications
The 193 HC Powerstar (Hesitation) Free Energy Band
Heating/Cooling Pneumatic Room Thermostat is an
excellent choice for saving energy by sequencing
heating and cooling valves. In most heat/cool pneumatic
applications, a 3 to 8 psig (21 to 55 kPa) heating valve
and a 10 to 14 psig (69 to 103 kPa) cooling valve is used.
By design, this provides a 2 psi (14 kPa) deadband where
no heating or cooling is occurring. The hesitation feature
allows you to change the deadband range to a 3, 4 or 5
psi (21, 28, or 34 kPa) range to save energy. Refer to the
Input/Output chart below for more information.
Description
Providing proportional, single output, dual setpoint,
2-pipe pneumatic room temperature control, the 193 HC
Powerstar (Hesitation) Free Energy Band Heating/Cooling
Pneumatic Room Thermostat is designed to sequence a
heating device or a cooling device.
The hesitation feature keeps the output pressure
constant through a 6°F (10.8°C) range (typical), causing
a deadband.
Features
Dual setpoint dials available in Fahrenheit or
Celsius scales
Sensitive bimetal responds to temperature changes
• Integral, eld adjustable limit stops
Adjustable Free Energy Band
Wall mounting plate for connection to a variety of
rough-in terminal boxes included
Test port for fast check of output pressure without
removing the cover
Field replaceable thermometer, setpoint dials,
restrictors, and lters
Options
Fixed limit stops to
meet government
speci cations
• Quick-connect air
connections for ease of
installation and service
Large, 1/2" setpoint
knob for convalescent
homes
Application Drawing
Input/Output Characteristics