Installation Instructions

Installation Instructions
Document No. 129-230
September 10, 2018
RC 195 Multiple Input Receiver-Controller
Item Number 129-230+2, Rev. CA Page 1 of 8
Product Description
The RC 195 Multiple Input Receiver-Controller is a
pneumatic instrument that can be used as a one
input (DA or RA), two input (DA or RA with reset), or
three input (DA or RA with reset and control point
adjust) instrument.
It produces a pneumatic control signal based on the
net pneumatic input and the mechanical settings,
such as set point, percent proportional band, and
authority.
Troubleshooting
Before troubleshooting the operation of the RC 195
Multiple Input Receiver-Controller, check the
following:
supply pressure at the unit is 22 2 psi
(152 kPa)
transmitter input being used is between 3
and 15 psi (21 to 103 kPa)
only one restrictor supplies the transmitter
transmitter calibration is correct
Contents
RC 195 Multiple Input Receiver-Controller
Custom labels for connector identification
Stick-on scales for setpoint dial
Scale conversion card
Product Number
195-2000
The RC195 Multiple Input Receiver-Controller
replaces the products listed in Table 1.
Table 1. Cross Reference.
Manufacturer
Product Number
Barber-Colman
RKS-3002
RKS-4002
Honeywell
PR908B
RP920B
Johnson Controls
T-5800-3
Robertshaw/Siebe
P341
P541
Required Tools
Flat-blade screwdriver
Two No. 8 or No. 10 screws
RC 195 Simulator for calibration of two and
three inputs
Expected Installation Time
45 minutes
Table 2. Troubleshooting Chart.
Check
Probable Cause
Corrective Action
Rotate setpoint
adjustment screw
counterclockwise
Pressure
increases
Transmitter sensing medium which is
above (RA) or below (DA) the
proportional band
None
Receiver-controller out of calibration
Recalibrate
Pressure remains
unchanged
Plugged pilot relay restrictors
Replace pilot relay
restrictors
Receiver-controller is defective
Replace receiver-controller
Rotate setpoint
adjustment screw
clockwise
Pressure
decreases
Transmitter sensing medium which is
above (DA) or below (RA) the
proportional band
None
Receiver-controller out of calibration
Recalibrate
Pressure remains
unchanged
Receiver-controller is defective
Replace receiver-controller