Data Sheet for Product
Pressure Independent
Control Series
Technical Instructions
Document No. 155-774
May 18, 2021
Two-Way, Brass Valve
Bodies, 1/2-Inch to
2-Inch, ANSI 250
1/2 to 1-1/4 Inch NC
1/2- to 1-1/4-Inch NO
1-1/2 to2-Inch NO
Siemens Industry, Inc.
Description
Siemens Pressure Independent Control Valves integrate three functions into a single
device: control valve, adjustable flow limiter, and automatic pressure regulator. The
1/2- to 1-1/4-inch Normally Open and 1/2 to 1-1/4 inch Normally Closed Valves have
a 2.5-, 5- or 5.5-mm stroke, and a threaded valve bonnet for use with SSD Electronic
Valve Actuators. The 1-1/2- and 2-inch Normally Open Valves have a 15-mm stroke
and use the SAY Electronic Valve Actuators.
Features
• Control valve with integrated pressure regulator and adjustable flow limiter.
• ANSI Class 250 valve body.
• 200 psi close-off with ANSI Class IV leakage (1/2 to 1-1/4-inch Normally Open).
• 100 psi close-off with ANSI Class IV leakage (1-1/2- and 2-inch Normally Open).
• 45 psi close-off with ANSI Class IV leakage (1/2 to 1-1/4 inch Normally Closed).
• Linear Flow Characteristic.
• Stainless Steel Stem.
• 1/2- to 1-1/4-inch valves do NOT include P/T ports. If P/T ports are required, the
599-10079 P/T ports accessory kit must be ordered separately (see Accessory).
• 1-1/2- and 2-Inch Valves include P/T ports.
• SAY actuators for 1-1/2- and 2-inch Normally Open Valves can also be set for
Normally Closed operation (reverse acting). See note on page 2.
Application
For use in HVAC applications with Pressure Independent Control SSD, or SAY
Electronic Actuators, to control hot or chilled water or 50% water-glycol solution in
closed loop systems.
Product
Numbers and
Ordering
Valves can be ordered with or without an actuator assembly from the factory. See all
orderable valve part numbers in Table 1. For all valve/actuator assembly part
numbers, see Pressure Independent Control 2-Way Valves and Electronic Valve
Actuators Submittal Sheet (154-087).
Warning/Caution
Notations
WARNING:
Personal injury or loss of life may occur if you do not
perform a procedure as specified.
CAUTION:
Equipment damage may occur if you do not perform
a procedure as specified.