Data Sheet for Product

Technical Instructions Pressure Independent Control
Document No. 155-773 SSD Series Electronic Valve Actuators
May 8, 2019
Page 6 Siemens Industry, Inc.
Manual Override
The actuator can be driven manually to any position between 0 and 1 with a 3 mm hex
wrench. The control signal from the controller, however, will take priority over any
manual position.
For manual positioning (without power), insert the 3 mm hex wrench in the center of the
position indicator. See Figure 7. The actuator will maintain its position until power is
provided or restored.
Figure 7. Manual Override Operation.
(A) Turn hex wrench counterclockwise to retract the spindle.
(B) Turn hex wrench clockwise to extend the spindle.
NOTE: Do not perform manual override while the power supply is connected; the
actuator will not track accurately when the control signal is applied. A short
power off/power on sequence is recommended to recalibrate the SSD61U
actuator.
Wiring
Do not use autotransformers. Use earth ground isolating step-down Class 2 power
supplies.
Determine supply transformer rating by summing total VA of all actuators used.
It is recommended that no more than 10 actuators be powered by one transformer.
Because the triacs on TECs and DXRs always switch hot power, add a 1000 Ohm
2-Watt resistor across each of the binary (Y1, Y2) outputs (see Figure 12). The two
resistors must be used for all hot-switching triacs not just TEC and DXR.
Figure 8. SSD81U Wiring Diagram.
WARNING:
Terminal connection G0 is Common,
not ground.
Figure 9. SSD61… Wiring Diagram.