Data Sheet for Product

Technical Instructions Pressure Independent Control Series Two-Way Valve Bodies
Document No. 155-774
May 18, 2021
Page 6 Siemens Industry, Inc.
Commissioning
Notes
CAUTION:
The Pressure Independent Control Valves must be open when
flushing or pressure testing the system. Strong pressure impacts
can damage closed Pressure Independent Control Valves.
CAUTION:
Differential pressure across the valve greater than 58 psi will result
in damage to the pressure regulator.
Dimensions in Inches (mm)
Valve P/N
Valve Size
Inch
S
L1
L3
L4
H2
H3
H
Weight
lb (kg)
599-04320
1/2
1.1 (27)
3.0 (75)
1.6 (41)
1.5 (38)
2.6 (67.3)
3.2 (82.4)
14.6 (371)
1.1 (0.50)
599-04321
599-04322
3/4
1.25 (32)
3.1 (79)
1.6 (41)
1.5 (38)
2.7 (67.5)
3.3 (82.5)
14.7 (374)
1.2 (0.53)
599-04323
1
1.5 (40)
4.0 (100)
1.7 (44)
2.5 (65)
3.4 (86)
4.0 (100)
15.4 (391)
2.8 (1.27)
599-04314
1-1/4
1.8 (46)
4.1 (104)
2.1 (53)
2.5 (65)
3.4 (86)
4.0 (100)
15.4 (391)
2.8 (1.27)
599-04315
1-1/2
2.3 (58)
5.4 (138)
2.7 (68)
3.7 (94)
5.9 (149)
20 (508)
7.2 (3.28)
599-04316
2
2.8 (72)
5.4 (138)
2.9 (74)
3.7 (94)
5.9 (149)
20 (508)
8.2 (3.71)
Figure 2. Two-Way Normally Open Valves Dimensions.