Removing the Actuator from a Valve,
Continued
5. Crank the actuator stem away from the valve
stem enough to enable removal of the anti-
rotation device.
6. Use a 2.5 mm hex wrench to loosen the anti-
rotation device set screw.
7. Slide the anti-rotation device off the valve stem,
and remove from the actuator arm.
8. Using a 6 mm hex wrench, loosen the two hex
head cap screws on the bonnet connection. See
Figure 19, Step 1.
NOTE: Only loosen the screws until flush with
brackets; do not remove.
9. Pull straight up on the actuator to remove from
the valve. See Figure 19, Step 2.
Figure 19. Removing the Actuator from the Valve.
> 4 in. (100 mm)
Minimum mounting distance to wall or ceiling, for mounting, connection,
operation, maintenance, and so on.
►►
> 8 in. (200 mm)