Removing the Actuator from a Valve, 
Continued 
5.  Crank the actuator stem away from the valve 
stem enough to enable removal of the anti-
rotation device. 
6.  Use a 2.5 mm hex wrench to loosen the anti-
rotation device set screw. 
7.  Slide the anti-rotation device off the valve stem, 
and remove from the actuator arm. 
8.  Using a 6 mm hex wrench, loosen the two hex 
head cap screws on the bonnet connection. See 
Figure 19, Step 1. 
NOTE:  Only loosen the screws until flush with 
brackets; do not remove. 
9.  Pull straight up on the actuator to remove from 
the valve. See Figure 19, Step 2. 
Figure 19. Removing the Actuator from the Valve. 
► 
> 4 in. (100 mm) 
Minimum mounting distance to wall or ceiling, for mounting, connection, 
operation, maintenance, and so on. 
►► 
> 8 in. (200 mm) 