Specifications

7SR242 Duobias Applications Guide
Scheme 2 (Intermediate)
BI
+ve -ve
TRIP COIL
52a
52a
52b
-
Circuit
Breaker
+
BO 1 BO n
Remote
Alarm
BO
R
H6 Scheme Notes:
Resistor:
30V dc Nominal: R = 3K9
48V dc Nominal: R = 5K6
110V dc Nominal: R = 15K0
TRIP CCT n FAIL
Figure 5-5: Trip Circuit Supervision Scheme 2 (H6)
Scheme 2 provides continuous Trip Circuit Supervision of trip coil with the circuit breaker Open or Closed. It does
not provide pre-closing supervision of the connections and links between the tripping contacts and the circuit
breaker and may not therefore be suitable for some circuits which include an isolating link.
1
Scheme 3 (Comprehensive)
Figure 5-6: Trip Circuit Supervision Scheme 3 (H7)
Scheme 3 provides full Trip and Close supervision with the circuit breaker Open or Closed.