Specifications

7SR242 Duobias Applications Guide
6.4 Transformer with Primary Connections Crossed on One
Winding
Reversing the connections on only one side of the transformer will reverse the phase sequence of the system. For
this arrangement W1 and W2 CT secondary wiring must be crossed over to replicate the crossovers on the
transformer primary connections – see fig. 6.5-1.
Figure 6-7 Dyn11 Transformer with Reverse Phase Notation
Notes:
The 7SR24 relay is set to correspond to the vector group shown on the main transformer rating plate i.e. Dy11,
+30°.
Relay instruments will indicate ’transformer’ quantities rather than system quantities.
©2010 Siemens Protection Devices Limited Chapter 7 Page 54 of 56