Wiring
Figure 6. SSA/P61U Wiring Diagram. Figure 7. SSA81U Wiring Diagram.
Do not use autotransformers.
Use earth-ground isolating, step-down, Class 2, power supplies.
Determine supply transformer rating by summing total VA of all actuators used.
Use one transformer to power up to 10 actuators.
WARNINGS:
Wire connection G is 24 Vac HOT on the SSA/P61U, not neutral.
G0 and G must be properly wired for correct function and full life of
the actuator.