Data Sheet for Product

SSA/P Series Electronic Valve Actuator Technical Instructions
24 Vac Floating or 0 to 10 Vdc Control Document Number 155-710
January 12, 2018
Siemens Industry, Inc. Page 5
Manual Override
The actuators can be driven manually to any position between 0 and 1 with a 3 mm hex key.
The actuator will maintain its position until power is provided or restored. A control signal
from the controller, however, will take priority over any manual position.
NOTES:
Do not perform a manual override while the power supply is connected: The
actuator will not track properly when the control signal is applied. A short power-
off/power-on sequence is recommended to recalibrate the actuator.
To hold the actuator in the manually set position, the connecting cable must be
unplugged.
Position Indicator at 0 Position Indicator at 1
Figure 8. Position Indicator.
NOTE:
The 0 and 1 position
markings are for
reference only and not
for stroke measurement.