Installation Instructions

599 Series Zone Valves
Installation Instructions
Document No. 129-346
December 3, 2009
SSA/P Electronic Zone Valve Actuator
24 Vac Floating or 0 to 10V Control
Fail-in-Place
Item Number 129-346, Rev. DA Page 1 of 4
Product Description
The SSA/P actuator requires 24 Vac, Class 2 power, and
a 0 to 10 Vdc or floating control signal to control 599
Series Zone Valves with 1/10-inch (2.5 mm) stroke.
Warning/Caution Notations
WARNING:
Personal injury/loss of life may
occur if you do not follow a
procedure as specified.
CAUTION:
Equipment damage, or loss of
data may occur if you do not
follow the procedures as
specified.
Product Numbers
Description
Actuator
Code
SSA81U
Normally Closed Floating
244
SSA61U
Normally Closed 0 to 10 Vdc
245
SSP61U
Normally Open 0 to 10 Vdc
248
Contents: One actuator
Required Tools
Small flat-blade screwdriver
Wire stripper
Estimated Installation Time
20 minutes
Prerequisites
WARNING:
If mounting the actuator to a valve
already in line:
Close the shut-off valves in the
piping (upstream first, then
downstream);
Or
Switch off the pump to allow the
differential pressure in the valve to
drop.
Figure 1. Acceptable Mounting Positions. *
*The vertical position is recommended for mounting.
WARNING:
Disconnect the controller power before
replacing the actuator.