Data Sheet for Product

Powermite 599 Series MT Terminal Unit 3-way Valves Technical Instructions
Document Number 155-197P25
October 27, 2015
Siemens Industry, Inc. Page 3
Table 3. Maximum Water Capacity - U.S. Gallons per Minute.
Valve
Size
inches
Pressure Differential - psi
Cv\1
2 3 4 5 6 8 10 15 20 25 30 40 50 60 75
1/2
0.4 0.6 0.7 0.8 0.9 1.0 1.1 1.3 1.5 1.8 2.0 2.2 2.5 2.8 3.1 3.5
0.63
0.9 1.1 1.3 1.4 1.5 1.8 2.0 2.4 2.8 3.2 3.5 4.0 4.5 4.9 5.5
1.0 1.4 1.7 2.0 2.2 2.5 2.8 3.2 3.9 4.5 5.0 5.5 6.3 7.1 7.8 8.7
1.6 2.3 2.8 3.2 3.6 3.9 4.5 5.1 6.2 7.2 8.0 8.8 10.1 11.3 12.4 13.9
2.5 3.5 4.3 5.0 5.6 6.1 7.1 7.9 9.7 11.2 12.5 13.7 15.8 17.7 19.4 22
4 5.7 7 8.0 8.9 10 11.3 12.6 15.5 17.9 20.0 21.9 25 28 31 35
3/4 6.3 8.9 10.9 12.6 14.1 15.4 17.8 20 24 28 32 35 40 45 49 55
1 10 14.1 17.3 20 22 24 28 32 39 45 50 55 63 71 77 87
Table 4. Maximum Water Capacity - Cubic Meters per Hour (m
3
/hr).
Valve
Size
Pressure Differential - kPa
inch
(mm)
1 10 20 30 40 50 60 80
Kvs/
100
150 200 300 400 500
15
0.03
0.11
0.15
0.19
0.22
0.24
0.26
0.30
0.34
0.42
0.48
0.59
0.68
0.76
0.05
0.17
0.24
0.30
0.34
0.38
0.42
0.48
0.54
0.66
0.76
0.94
1.08
1.21
0.09
0.27
0.38
0.47
0.54
0.60
0.66
0.76
0.85
1.0 1.2 1.5 1.7 1.9
0.14
0.43
0.61
0.75
0.87
0.97
1.06
1.23
1.37
1.7 1.9 2.4 2.7 3.1
0.21
0.68
0.96
1.17
1.35
1.51
1.66
1.91
2.15
2.6 3.0 3.7 4.3 4.8
0.34
1.1 1.5 1.9 2.2 2.4 2.7 3.1 3.4 4.2 4.9 6.0 6.9 7.7
20 0.54
1.7 2.4 3.0 3.4 3.8 4.2 4.9 5.4 6.7 7.7 9.4 10.9
12.1
25 0.86
2.7 3.8 4.7 5.4 6.1 6.7 7.7 8.6 10.5
12.2
14.9
17.2
19.2