Installation Instructions

Document No. 129-253
Installation Instructions
May 8, 2019
Siemens Industry, Inc. Page 3 of 5
Calibration Stroke
The SSC Series writes its calibration stroke parameters to
nonvolatile memory on the first start-up of the actuator.
Successive start-ups bypass the calibration stroke unless
the memory is manually cleared. If installing the actuator
on a different valve (such as on a replacement valve),
manually clear the calibration stroke from memory as
follows:
1. Remove the terminal cover using a Phillips head
screwdriver.
2. Locate hole on the circuit board with the shorting bars
(Figure 5).
3. With power applied to the unit, insert and gently twist
a flat-blade screwdriver to electrically connect the
shorting bars. The SSC… then performs a new
calibration stroke.
4. Secure the terminal cover back in place.
Figure 5. Manually Clearing Calibration Stroke from
SSC61U and SSC61.5U Nonvolatile Memory.
Wiring
All wiring must conform to NEC and local codes and
regulations.
Use earth ground isolating, step-down Class 2
transformers. Do not use autotransformers.
Determine the supply transformer rating by summing
the total VA of all actuators used. The maximum rating
for a Class 2 step-down transformer is 100 VA.
Do not power more than 10 actuators with one
transformer. (Use 0.5 amp on secondary actuators.)
Y2: Retracts actuator shaft
Y1: Extends actuator shaft
G: System potential
Figure 6. SSC81U NSR Floating Control.
Figure 7.
For Non-Triac Driven
Controllers.
Figure 8
For Triac Driven Controllers,
(TEC, DXR, and Others).
SSC81.5U Floating Control SR Hot-Switch.
G, G0: 24 Vac Y1 Extends actuator shaft
operating voltage G System neutral
Y2: Retracts actuator shaft G0 System potential (switched)
CAUTION:
Terminals must be properly wired for
correct function and full life of the actuator.
Because the triacs on TECs and DXRs
always switch hot power, add a 1000 Ohm
2-Watt resistor across each of the binary
(Y1, Y2) outputs (see Error! Reference
source not found.). The two resistors
must be used for all hot-switching triacs not
just TEC and DXR.
G, G0: 24 Vac operating
voltage
Y2: Retracts actuator shaft
Y1: Extends actuator shaft
G: System potential
G0: System neutral
(switched)
Figure 9. SSC81.5U Floating Control SR Neutral
Switching Applications.
NOTE: For proper operation, it is recommended no
more than three actuators be assigned to any
single control signal.