Data Sheet for Product

Technical Instructions Powermite 599 Series MT Terminal Unit 3-Way Valves
Document Number 155-197P25
October 27, 2015
Page 4 Siemens Industry, Inc.
Figure 1. Water Capacity Graph.
Selection Example
See Figure 1.
Select a valve given:
Required flow = 20 gpm.
Desired pressure drop = 5 psi.
Choose a 1-inch (25-mm) valve, Cv 10.