Start-up, Continued
1
2
Figure 11. SKD Electronic Features.
DIP Switches
(Left to right)
1
Selection of
Control Signal
2
Selection of
Flow Characteristic
ON
4 to 20 mA
Modified*
OFF
Factory Setting
0 to 10 Vdc
Default
*Changing the default setting will modify an equal percentage valve to a linear flow characteristic.
When set to default, the flow characteristic is determined by the valve body.
Normally Closed Valve
Actuator pressure cylinder moves:
Outward (0 to 1): Valve opens.
Inward (1 to 0): Valve closes.
Normally Open Valve
Actuator pressure cylinder moves:
Outward (0 to 1): Valve closes.
Inward (1 to 0): Valve opens.
Three-Way Valve
Actuator pressure cylinder moves
Outward (0 to 1): Valve opens between port NC and C.
Inward (1 to 0): Valve opens between ports NO and C.
The measuring voltage at terminal U provides valve stem position feedback to an