Data Sheet for Product

Flowrite 599 Series SKB/C Electronic Valve Actuator Proportional Control Technical Instructions
Document Number 155-163P25
September 25, 2018
Siemens Industry, Inc. Page 7
Start-up,
Continued
Standard Features
1
2
Figure 10. DIP Switches.
DIP Switches
(From Left to Right)
1
Selection of
Control
Signal
2
Selection of
Flow
Characteristic
ON
4 to 20 mA
Modified*
OFF
(Factory Settings)
0 to 10 Vdc
Default
* Changing the default setting will modify an equal percentage valve to a linear flow characteristic.
When set to default, the flow characteristic is determined by the valve body.
Normally Closed Valve
Actuator pressure cylinder moves:
Outward (0 to 1): Valve opens.
Inward (1 to 0): Valve closes.
Normally Open Valve
Actuator pressure cylinder moves:
Outward (0 to 1): Valve closes.
Inward (1 to 0): Valve opens.