s Desigo™ Insight Operating the management station, V6.
Siemens Switzerland Ltd Building Technologies Division International Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58-724 24 24 www.siemens.com/buildingtechnologies Siemens Building Technologies Desigo Insight, Operating the management station, V6.
Contents 1 About this document ........................................................................... 6 1.1 1.1.1 1.1.2 1.1.3 1.1.4 1.1.5 Before you start ..................................................................................... 6 Trademarks ........................................................................................... 6 Copyright ............................................................................................... 6 Quality assurance ..............................
5.5 Manually connect/disconnect a site ...................................................... 46 5.6 System time......................................................................................... 49 5.7 Start programs manually ...................................................................... 51 5.8 Create and delete user ........................................................................ 52 5.9 Lock ....................................................................................
8.5 Adjust the alarm handling system....................................................... 115 8.6 Route alarm messages to output devices ........................................... 115 8.7 Alarm configuration with System Configurator .................................... 117 8.8 8.8.1 8.8.2 Routing alarms using the Alarm Router .............................................. 137 Alarm Router functions ...................................................................... 137 Edit routing groups .....
1 About this document 1.1 Before you start 1.1.1 Trademarks The trademarks used in this document are listed together with their legal owners in the table. The use of these trademarks is subject to international and national statutory provisions. Trademarks BACnet™ CitectSCADAä Microsoft … Windows 7 Windows 10 Windows Server 2012 Windows Server 2016 SQL Server 2014 Legal owner American National Standard (ANSI/ASHRAE 135-1995) Schneider Electric (Australia) Pty Limited see citect.
1.1.4 Document use/request to the reader Before using our products, it is important that you read the documents supplied with or ordered at the same time as the products (equipment, applications, tools etc.) carefully and in full. We assume that persons using our products and documents are authorized and properly trained and have the requisite technical knowledge to use our products as intended.
Caution 1.4 Document conventions 1.4.1 Symbols used Users with access can change or delete data. When you see the symbol to the left, data may be lost irretrievably. Tip The symbol to the left denotes information that helps you properly operate and use the programs. This information is based on experience; we strongly suggest that you observe all hints. Important note: Important information is printed on a gray background. 1.4.
Buttons Buttons are displayed in bold. Example: When you click Cancel, the ... Example: Apply. This tells you to click the Apply button. Menus and menu items Names of menus and menu commands are printed in bold format. Example: Click New Meter in the Dimensions menu Dialog box element designations precede the actual designation. Example: Select the appropriate date in the spin box Account Expires.
Mouse click In command sequences, right-click and double-click are mentioned specifically. For all other cases, left-click the selections. Context menus Right-clicking normally opens a context menu. Date and time format Display of date and time depends on the settings of your Windows installation. 1. 2. 1.5 Document structure Select Start>Settings>Control Panel>Regional Settings. Select the Time tab in the Regional Settings dialog box to define the format.
Describes the functions available for the logging of events and their retrieval by the user. 11 Report Viewer This section describes the functions used to collate plant data to produce a report. 12 Event program (Reaction Processor) This section describes the functions which influence events transmitted to or received from the system. 13 Scope This section describes functions defining user-specific object access. 14 Eco Viewer This section describes the functions used to assess a plant's efficiency.
2 Security 2.1 Cyber Security Disclaimer Cyber security disclaimer Siemens products and solutions provide security functions to ensure the secure operation of building comfort, fire safety, security management and physical security systems. The security functions on these products and solutions are important components of a comprehensive security concept. It is, however, necessary to implement and maintain a comprehensive, state-of-theart security concept that is customized to individual security needs.
3 Chapter overview System overview This chapter provides an overview of general, user-relevant aspects of Desigo Insight. 3.1 Features of the system philosophy The Desigo Insight management station software is object-oriented and has a modular structure. It is based on a wide range of standard technologies including: · · · · · · · · Operating systems: Windows 7, Windows Server 2012.
3.3 Architecture Software architecture The following images provide an overview of the internal structure of the Desigo Insight management station software. 3.4 SQL database (password guidelines) Desigo Insight an SQL database to store data. Siemens requires you to changes the Desigo Insight default password for the SQL database to prevent Desigo Insight from becoming a target of hacker attacks (refer CM110591 Installation and configuration chapter 6.7.17 SQL System Administrator Password Management).
Alarm Router Alarm Router dispatches the alarm messages to the selected receivers (e.g. printers, e-mail, fax, pagers or mobile phones). Time Scheduler Time Scheduler allows central programming of all time-controlled building services functions, including individual room control. Trend Viewer Historical and real-time processing of data, for convenient analysis of off-line and on-line trend data. Used to optimize plant operation.
3.6 Philosophy User access philosophy The management station software offers a highly flexible means of defining an environment ideally suited to each user. It is possible to specify which user(s) should be allowed access to which sites and buildings, and which Desigo Insight applications each operator may use. Users in a building can be grouped logically according to their tasks (e.g. caretaker, building manager, maintenance engineer), each of these “user groups” having a dedicated set of privileges.
Scopes Freely definable scopes (e.g. range scope, discipline scope) allow for customizing project data views (e.g. lighting control visible only to electricians, not heating engineers). Automation system access The system can be set up to allow a variety of media (Ethernet, LON, PTP) access to the automation system. 17 / 146 Siemens Building Technologies Desigo Insight, Operating the management station, V6.
General 4 General operation 4.1 Conventions and style Desigo Insight is operated with the mouse. As a consequence, we do not make special reference to key commands. Unless otherwise stated, mouse and keyboard operation is based on the Windows 7 conventions. Note A mouse or other pointing device is always required. Desigo Insight cannot be operated from the keyboard only. Mouse operation The left mouse button is normally used to select or select an option.
The right mouse button is normally used to display context menus, (i.e. short-cut menus related to a specific item or area on the screen). The instruction "Right-click Alarm Acknowledge in the Event column and select Filter by Alarm acknowledge" means: 1. 2. Place the cursor over a selected Alarm Acknowledge entry (see below) and right-click to display the associated context menu, then Left-click Filter by “Urgent” in the context menu.
Step 3 Windows User logon Step 4 Building properties Step 5 1. 2. 3. 4. Start Desigo Insight. Logon as Administrator. Click "System Configurator" on the Desigo Insight taskbar. Create the user as a Windows login. 5. 6. Click the No Password checkbox. Click OK > OK. 1. Select Desigo Insight building automation and control system in the System Configurator Browser. Right-click to open the properties dialog box. Select Windows from the Authentication Mode list box. 2. 3. 1. Site Properties 2. 3. 4.
4.3 User privileges Scope Only authorized users have access to the Desigo Insight system. When you enter your user name and password, the system checks your user privileges to determine, for example, the programs to which you have access and the sites to which you can connect. No access If a user has not been assigned the necessary privileges to perform a given operation, this is indicated in one of the following ways: · The associated menu option may be "grayed out" (dimmed).
Displaying ToolTips Example: Place the mouse pointer over one of the buttons on the Desigo Insight taskbar. Reference For more detail on special application of tool tips in Plant Viewer, refer to Chapter "Plant viewer operation“ in this manual. 4.5 Basic principles Working with the Desigo Insight program window The Desigo Insight program windows are modeled on Microsoft Windows, and can be manipulated in the same way. Close Menu bar Maximize Toolbar Minimize Status bar Minimize 1.
4.6 Program start based on time Automatic third-party program start based on time It is possible to have your system configured so that one or more third-party programs start at a specified time. This could be useful for spreadsheet and analysis programs. You might, for example, want to run a spreadsheet program every Monday morning to check the hours-run readings from fans and pumps. Tip Ask your Desigo Insight expert to configure a program so that it starts automatically at a specified time. 4.
Example 1: Object Viewer to Alarm Viewer 1. 2. 3. 4. 5. Click the Object Viewer on the Desigo Insight taskbar. Expand the view in System Browser until you can see all the relevant data points in the System View. Active alarms are indicated by a red alarm symbol on the relevant site, device and object icons. Right-click the object symbol to display a context menu. Point to Send To >. Click the required program (in this case Alarm Viewer). This operation launches the program if it is not already open.
4.9 Operate the Desigo Insight programs 4.9.1 Personalize the workspace The programs in the Desigo Insight system allow you to personalize the workspace to suit your own preferences and specific needs.
4.9.3 Function Working with the System Browser System Browser is an ideal tool for navigating through the various levels of your system. It provides comprehensive information about the automation and control system hierarchy in all the available sites. The information is displayed in a tree structure similar to that used in the Windows Explorer. Display: Site>Device>Object>Property and status (e.g.
4.9.4 View data As is the case with System Browser in all other Desigo Insight applications, the user can decide whether to view the data using the Technical View, User View or System View. Select view System Browser provides two identical tree structures, in a format similar to that used in the Windows Explorer. 1. Technical View Select menu View > View. Selecting the Technical View gives you a generic view of the automation and control system. e.g. Site:A’Ahu’FanEh’Cmd.FbVal.
Note · · The user view is individually created for each building automation system. It is otherwise empty if not engineered for your plant. Desigo Insight supports variable or set user designations that can be defined individually for each site. Only one type can be defined for the site-independent part. The project determines which type is used in the project.
Symbols The following symbols denote BACnet objects.
Object properties Symbol Desigo PX data type Real Integer Multistate Digital Time Date Time and date Bit set String Array, list Unknown I/O address Find objects If you have problems finding certain folders, sites, devices or objects in either the System View or the User View of the System Browser tree, you can use the Find function described here to locate them. Frequently used objects can be added to the Favorites folder as described further on in this section. 1. Click "Find" on the toolbar.
6. 7. 8. 9. 10. Click OK. Enter the short name in the Name field (e.g.: FanSu). Enter a description (e.g. supply air fan) in the Description field. In the Find Hierarchy field, enter the number of hierarchies to be found. Click OK in the Search field to start the search. The Dialog box Find in opens. All data points matching the search criteria are listed (name and path). 11. Right-click the desired object and select the corresponding function.
4.9.5 Setup workspace Set up the workspace for Alarm Viewer and Log Viewer The user can customize the workspace as follows: · · · · · · Show/hide the toolbar Show/hide the status bar Show/hide System Browser Show/hide columns Modify column width and order Modify grid line display Note The workspace settings listed above are stored on a user-specific basis and is applied automatically when next started by that user. Toolbar 1. From the View menu, select to show or hide the Log Viewer toolbar.
You can also double-click column divider to modify the column width. Note The column size cannot be set to zero. Refer to "Define columns" to show/hide columns. Change grid settings Grids can be shown or hidden. 1. 2. Reset workspace settings 3. From the View menu, Show Grid. Enable/disable the display of grid lines separately for horizontal and vertical lines. Click OK to apply the new settings. 1. Select Tools > Setup workspace to rest default workspace settings. 4.9.
Reference For details of how to use the Find function and the associated search criteria: Refer to chapter "General Operation" in this manual. 4.9.6.1 Filter events lists Filter view Filtering the view produces a subset of the complete database. If required, the view can be filtered by more than one criterion simultaneously.
1. 2. Custom filter Left-click the item(s) you want to use as filter criteria. You can select a combination of options by holding down the or key while making your selection. The filtered view is included only events which match one of the selected criteria. Click Filter to filter the view. This function cannot be used in the Event Group and Comment columns. 1. 2. 3. 4. Place the cursor on a field in the column by which you want to filter the view. Right-click to display the context menu.
Example 4: Custom Filter dialog box for the priority column (priorities selected here correspond to the priorities on the management station). 5. Click OK to start the filter process. Tip The three most recently used filter attributes for each column can be found and recalled from the context menu (right-click). See also “Operating Log Viewer” above for the structure of the context menu.
Remove Filters Remove all filters from a view. 1. Right-click the view. Select View > Remove filter. OR on the toolbar. Click "Remove Filter" OR Select menu View > Remove Filter. Remove one specific filter criterion. 1. Right-click the relevant column. Select Remove. 4.9.6.2 What is a filter query? Saving and applying filter queries Currently applied filters can be saved as a set of criteria referred to as a “filter query”.
Rename filter queries 3. 4. 5. Click More to display a list of all queries in the system. Select queries you want to copy to the list of personal queries. Click Copy. 1. 2. Select Filter > Predefined to display the list of existing filters. Select the query to be renamed and click it a second time (slower than a double click) or right-click and select Rename. You are now in the edit mode. Edit the filter name.
Remove sorting 1. Click the relevant column heading until sorting is removed. – The column is sorted in ascending order at the first click. – The second click results in a sort in descending order. – A third click removes the sort in this column. Remove sorting from all columns 1. Select View > Remove Sorting. OR Click "Remove sort" OR Right-click to open context menu and select Remove Sort. 4.9.
comes inaccessible, and Zoom in becomes active. Closes the Print Preview and returns to the standard document view. Printing a document 1. 2. 3. 4. 5. Print a ‘snapshot’ of the screen 1. 2. 3. Click Print in the menu or print on the application toolbar. The Print dialog box appears. Check that the printer shown in the Printer dialog box is the one you want to use. If not, scroll through the list to find the correct printer. Specify the page range where appropriate.
5 Chapter overview Start Desigo Insight This chapter describes how to start Desigo Insight, shut down and how to add or delete a user with the proper authorization. 5.1 Start Desigo Insight Automatic start Your Desigo Insight is normally configured to automatic startup when the computer is turned on. Installation modifications for automated start or after a power outage are described in the section "Installation modification". Manual start 1. 2. 3.
5.2 Manual Login 1. Click any of the buttons on the Desigo Insight taskbar to display the Log On Shell dialog box. Standard Special 2. Enter your user name and password. Note that the password is case-sensitive. 3. Click OK. If your system has been configured to connect to a site or start a Desigo Insight program automatically, the connection is established or the program is started when you log in. Note for Windows users When you log in as a Windows user, this login window does not appear.
Password policy If required, a more stringent password policy can be applied. This must be defined under General in System Configurator and activated for the user concerned. With an active password policy, the following rules apply: · · · · The password must have at least n characters. The password must not have been used previously in the last n passwords. The password must not have been used in the last n days.
5.4 Display Display system and version information This is a special indicator, showing if there is a problem with the local management station. The symbol is always visible in the Desigo Insight taskbar, even when no user is logged on. The image displays the content of the Supervisor Information tab. 1. 2. Click the Desigo Insight button on the Desigo Insight taskbar Select Show > System information. OR Click system information , , on the taskbar.
Reset warning message Desigo Insight shows warnings that must be reset, e.g. if a folder changes during operations (storage on server). In this case, you must first adjust the folder and then acknowledge the warning in the Alarm Router. 1. 2. 3. Click in the Desigo Insight taskbar. Select View > Statistics…. The Task Statistics dialog box shows the message information. Click Reset. The warning messages are reset. Yellow: Red: Display version information 1. 2.
5.5 Manually connect/disconnect a site Definition of a site A site is an independent (from the user's point of view) and self-contained logical entity within the building automation and control system. A site is a means of structuring, and in general, consists of an area which is self contained in terms of location, function and organization (e.g. a building or a group of buildings). Manual connection 1. 2. 3. 4. 5. 6. Click Desigo Insight on the Desigo Insight taskbar and select Connect/Disconnect.
Green arrow displays from management station to automation station The connected site has devices that are not online. The same symbols are used to display the site connection state in the Connect/Disconnect site dialog box. Click Connect and Disconnect Sites on the Desigo Insight taskbar. Life check Life check allows you to check whether or not the appropriate site is still communicating with your management station. 1. 2. 3.
Taskbar information after connection to a site After a site connection is established, your user name appears on the taskbar to confirm your login. Further, the following changes are visible on the Desigo Insight taskbar: Buttons Details Measures A red clock in the time display indicates that the site time and the management station time are not synchronized, and that the time difference is greater than the predefined maximum.
5.6 Overview System time "System time" refers to the time clock in your building automation and control system. This includes the time at the PX automation stations and the time on the management station. Your system has several so-called "Real Time Clocks". As a rule, there is one per management station and one per PX automation station.
Check / Change If the system time is incorrect, and the site time is synchronized automatically to the management station time, then check the management station time. This is displayed in the lower right hand corner in the Windows taskbar. Double-click this time display to adjust it using the normal Windows interface. It is then usually sufficient to connect to site. In cases where the site time is not synchronized to the management station, you can adjust the site time as follows: Note 1. 2.
UTC UTC (Universal Time Coordinated) is a worldwide reference time, equivalent to GMT (Greenwich Mean Time). UTC may be used in the Desigo PX automation stations, one advantage being that daylight saving time changes are no longer necessary and hence the trend data and historical data does not suffer from gaps or compressions in clock time. The disadvantage is that human operators of the system prefer to work in “local time”.
Note You only see buttons for Desigo Insight applications to which you have authorized access. Tip You can use ToolTips to check which icon is associated with which program (point the cursor at a button to display its function). 5.8 Create and delete user Why create a user? A user login must be created for each Desigo Insight user to ensure clear identification of the interaction in Desigo Insight, e.g. acknowledging an alarm.
4. Enter the User name. The selected user name determines user authentication when starting Desigo Insight. – Desigo Insight user: Select any user name. – Desigo Insight Windows user: User name is identical to the Windows user name. – Windows user: The user name is identical to the windows user and must be defined as follows. 1. Click User is a Windows user. 2. Click Select Windows user. 3. Select a Windows user. 5. 6. 7. 8. 4. Click OK. The user name is defined. Define other user properties.
3. 4. Delete user Select Copy user. Enter the name of the new user and configure user properties as described below. To delete a user in the System Configurator. Click "System Configurator" 1. Right-click the user folder to be deleted. You can select several folders by holding the control key and left-clicking the desired folder. Select Remove. Click the key to delete one or more users. 2. 3. Yes Deletes the currently displayed user. Yes to All Deletes all pre-selected users without confirmation.
After a predefined period of inactivity on the part of the user (definable in System Configurator, default 15 minutes), Desigo Insight locks automatically to prevent unauthorized system access. Note for Windows users Desigo Insight is not automatically locked for Windows users. In this case, the desktop can be locked via Windows. To do this, select Display Properties > Screen Saver. Desigo Insight continues to run under the logged in user when the Desktop is locked under Windows.
Note After logoff, all background Desigo Insight (e.g. online trend) activities continue, the connection is automatically maintained through a standby user. User actions are only possible after the user logs in. If a user from a different user group logs in, this may cause activities such as online trend, which depend on user privileges, to be terminated. Not for Windows users A Windows user cannot log off Desigo Insight. This is the only way to ensure user authentication. 5.
5.12 Restart Note Restart Desigo Insight 1. Click Desigo Insight and select Restart. The dialog box Desigo Insight Lock, Log OFF and Shut Down opens. 2. 3. 4. Select Restart. Click OK. Desigo Insight is shut down and restarted. Log in under your user name. When you select Restart, Desigo Insight is ended on the management station. All site connections are disconnected. Activities such as online trend are ended (data normally are lost).
5.13.1 Connect to the terminal server In a network, any (configured) computer can access the Desigo Insight terminal server. 1. 2. Select Start > All Programs > Accessories > Communications > Remote Desktop Connection. The Remote Desktop Connection dialog box opens. 3. 4. 5. Enter the terminal server computer name (e.g.. chstaw0290). Click Connect. The Log On to Windows dialog box opens. 6. Enter all information. · User name: Personal user name on the terminal server computer.
Connection error If connection to the terminal server cannot be established, the following error message appears. 5.13.2 Start Desigo Insight (Remote Desktop) Start Desigo Insight 1. 4. Select Start > All Programs > Desigo Insight Vx.x > Desigo Insight. Desigo Insight starts (startup screen followed by Insight taskbar). Select a button on the Desigo Insight taskbar. The Log on to - Shell dialog box opens. Enter your user name and password. Note that the password is case-sensitive. Click OK.
Service active Check the system information in Desigo Insight Information Desigo Insight und contact Siemens Service. Service stopped Data cannot be edited or forwarded. Contact Siemens Service. Service started or is stopped If the status does not change after 60 s, contact Siemens Service. 60/146 Siemens Building Technologies Desigo Insight, Operating the management station, V6.
5.13.4 Disconnect connection to terminal server Disconnect the connection to the terminal server as follows. Shut down Desigo Insight 1. 2. 3. Click "Log off and shut down" Select Shut down. Click OK. Disconnect connection to terminal server 1. Select Start > Log Off. The Log Off Windows dialog box opens. Select Log Off. This disconnects the connection to the terminal server, closes the session and releases the license. 2. Note in the Desigo Insight taskbar.
6 Working with the Object Viewer Chapter overview This section provides all the information required by the user to operate the Object Viewer (plant data points are displayed in a browser) and the associated plant. What is the Object Viewer? The Object Viewer allows you to display detailed information about your building automation and control system, including information about individual objects by data point name, showing values, units and maximum and minimum limits.
Find Refresh View Disable value updates Opens a dialog box to enter search criteria to search for objects in the System Browser. Updates all objects. Manual refresh is required for the following cases: - An object property was changed manually. - A new site was connected. No object values are updated. Manual updating is unavailable (i.e. Menu View > View Update). Update visible values Update all values Supress Property not Supported Always on Top Only displayed object values are updated.
on top. Updates all objects. Manual refresh is required for the following cases: - An object property was changed manually. - A new site was connected. Opens a dialog box to set display options (application window, toolbar, status bar). Determines which object values to regularly update (i.e. in the object table or under Properties). Displayed in the status bar. o Update: Disabled. No object values are updated. Manual updating is unavailable (i.e. Menu View > View Update). o Update: Visible values.
object. Start Object Viewer Release Manual Releases manual entry. Send to Shows the object directly in the selected Insight program. Copy Copies the selected object's System Browser reference to the clipboard. Copy Citect Tag Copies the selected object's Citect tag to the clipboard. Copy Name Reference Copies the selected object's reference name to the clipboard. Properties Opens the dialog box with the properties of the selected object. 1.
views. The automation station is up-to-day and does not require a data import. The corresponding hierarchy stage is scanned online for underlying objects. Site is not imported. No automation station is imported. Displays the management stations found with the defined management station designation. The management stations are imported during the scan to the first site found (does not necessarily need to be the first on the alphabetic list).
6.1 Select a data point 1. 2. 3. Display detailed data point information from the Object Viewer Display System Browser if necessary by clicking the Show/hide System Browser button on the Object Viewer toolbar. Expand the System Browser view down the tree to display the required object. If you have problems locating the required object, use the Find function as described above. Click the object in the System Browser view to display detailed information in the contents pane of Object Viewer.
O Manually overwrite object. Q Default value is active R PXM10 / PXM20 or PXM10 / PXM20 or Desigo Insight has set Desigo Insight value. has set value Input not connected. No values have been - set Alarm not yet reset. Press S Output module on manual. Input module on manual. U Alarm not yet acknowledged. V Value object overwritten W Object overridden by external switch. X Alarm switched off Object is switched off via EnEvt. Y Object overridden by safety function.
Working with the Favorites folder To simplify navigation to frequently used objects, you can add them to the Favorites folder. You can then jump from Object Viewer to one of these objects as follows: 1. 2. Add to Favorites on the toolbar. Click Favorites From the list select the shortcut to the required object. You can add an object to the Favorites folder as follows: 1. 2. Rename or delete favorites Select the Favorites menu in Object Viewer to save your "Favorites".
3. 4. Click Rename to change the shortcut name. OR Click Delete to remove this data point. Click Close to close the Organize Favorites dialog box. 70/146 Siemens Building Technologies Desigo Insight, Operating the management station, V6.
6.1.1 Change object values and properties from Object Viewer Before you begin this procedure, make sure you are connected to the site. (You can check this from the connection indicator on the Desigo Insight toolbar, or by choosing Connect/Disconnect in the Desigo Insight menu.) 1. 2. Note Show System Browser. (See "Show/hide System Browser" earlier in this section.) Select the desired object. Expand the System Browser view as required. The object is displayed in the content window.
2. Select the Place data point in manual (i.e. overridden) state checkbox. Analog values: Change the value or state with: – Spin buttons – Slide Digital or multistate values: Change the value by selecting the state. 3. Caution Caution The lower write priority, the more safety precautions in Desigo PX can be bypassed. This may result in injury or damages due to unintended use! 4. Note Select the priority you want to use to write the output object.
6.1.3 Enable outputs After a fault is resolved, the set value must again be enabled. 1. 2. 3. 4. Tip Double-click attribute PrVal in the pane. Select the priority you used to write the output object. Select the Set NULL checkbox. Click Apply or OK. You can check the current BACnet priority by clicking the properties of PrioArr. Setting BACnet write priority Description Yes, Off Value active, Value = Off Yes, On Value active, Value = On No, This priority is not considered.
For more information on BACnet write priorities, see Documentation on basics CM110664, Section 24. 6.1.4 1. 2. 3. 4. 5. 6. Override parameter 1. 2. 3. Override inputs Double-click attribute OoServ (Out of Service) in the pane. The Properties dialog box is displayed. Select On. Click OK. Double-click attribute PrVal (Out of Service) in the pane. Select a value. Select On for digital inputs. Select the corresponding value for analog inputs. Click Apply or OK. The new value is sent to the field device.
6.1.7 Change user designation text During the engineering of a Desigo Insight subsystem, information such as the engineering unit, the precision of the value to be displayed and the minimum/maximum limit of every object in the automation system is imported into the Desigo Insight system database. These properties define the format of information displayed in Object Viewer and Plant Viewer.
6.2 Why instructions? Instruction texts to create alarms Instructions provide the user additional information an event (alarm) or an object in the user's plant. Informative instructions can help the user eliminate faults faster, at lower costs and with less stress or to introduce the appropriate measure to eliminate the fault. Since the texts are very project-specific, definitions are more logically created by the plant user (operator).
Create text These texts apply across site to avoid the need to newly define texts for each site in a project. 1. Click New to start the user text editor. 2. Define a unique name in the Name field, e.g. Fire alarm (max. 20 characters) and describe the appropriate measure in the large text field. Click OK > OK to save the data. OR Click OK > New to define the next entry. 3. Note Only users with the appropriate access can create or change instructions.
Text assignment The corresponding instruction can be assigned to every data point visible in the object structure. 1. 2. 3. General text Select the text you want to assign to the object. Click OK. The text is applied in the text dialog. Click OK or Apply to save the data. OR Click Cancel to reject the input. The corresponding, additional text can be assigned to every data point visible in the object structure. The input and assignment is the same as for the instructions.
7 Operate graphics Chapter overview This section provides all the information required by the user to operate graphics (Plant Viewer) and the associated plant. Start Plant Viewer 1. Note Your system may be configured so that Plant Viewer is launched automatically when you start Desigo Insight. Click the Plant Viewer 7.1 on the Desigo Insight taskbar. Layout of the Plant Viewer screen The Plant Viewer screen consists of the following basic areas: · Navigation bar.
2. From the options displayed, choose “Technical Designation”, “System Designation”, “User Designation” or “None”. Select: For… Technical designation … a text label based on the hierarchy of the BACnet objects. E.g. Site:A’Aoa’FanEh’Cmd.FbVal System designation … a text label based on the system address. e.g. Site:AS10’Vnt10’Fan’Cmd. User designation … a text description can display, for example: building, floor, plant type, plant number, data point type and number, etc. e.g.
Select page Opens a list box, from which you can select a graphics page to open. If engineered accordingly, the graphics pages may be displayed in a hierarchical structure. You may also be able to choose whether to open the selected graphics page in addition to, or instead of the currently open graphics page, depending on your user privileges. Top Page Opens the “Top” graphics page, i.e. the opening screen for your system. (This may be a photo of the building or a map of a building complex, for example).
Handling multiple windows with the buttons on the Plant Viewer navigation bar: Buttons Function Tile Horizontally Arranges all the open graphics pages on the screen. The graphics pages can be “tiled” (arranged horizontally or vertically) or “cascaded” (overlapping). Tile Vertically Cascade Select Window Selects an option from the list of open windows, and bring it to the foreground. Close Window Closes the active window Close All Windows Closes all currently open windows.
The navigation commands in the Page context menu have the same functions as the corresponding buttons on the Plant Viewer navigation bar (see above for a description). 7.4 Show / Hide Display/hide the navigation bar The navigation bar is displayed automatically when Plant Viewer is started, but it can be hidden and redisplayed as follows: 1. 2. Right-click anywhere on the background of a graphics page (but not over a symbol). Select Show Navigation Bar.
Note This project-specific help is not a part of standard delivery by Siemens; it must be ordered separately as needed. 7.5 Navigation methods Open graphics pages You can navigate between graphics pages in three main ways: · Buttons on the navigation bar · Options in the Page context menu · Engineered buttons and symbols on the graphics pages. This last method is described under “Operating the graphics” later in this section.
Note 1. Open a “Favorite” graphics page (i.e. one to which you know you want to return to frequently). 2. 3. Click Favorites on the navigation bar. Click Add to Favorites to add your selected open graphics page to the list. The graphics page name now appears in a drop-down list whenever you click the Favorites button. The Favorites list can hold a maximum of 20 graphics pages. Open Favorites 1. 2. Tip on the navigation bar to display a drop-down menu.
Genie Move the mouse cursor over a symbol and right-click. If the Object context menu opens, this indicates that there is an object linked to that symbol. Symbols of this type are referred to as Genies. Releases from manual state. Display object property sheet. Navigate to other Desigo Insight programs via object name or property name Example of an Object context menu invoked by a right-click a Genie. Super-Genie Move the mouse cursor across the graphics page.
7.7 Mouse use Navigating in graphics pages larger than the screen Graphics operation principles Because of the significance of the context menus in Plant Viewer, it is important to note the following conventions for operating the mouse within a graphics page: Action Result Right-clicking an operable symbol displays the Object context menu Executes an action, for example, opens a Super-Genie, operating a button. Right-click Displays a context menu.
Keyboard shortcuts The following default shortcuts are defined in Plant Viewer: Keys Function F1 Start project-specific help (if available in your project) Alt+F4 Close Plant Viewer Alt+P Open the Page selection menu Home Open the Top page Alt+0..9 Open Favorite graphics page 0..9 Ctrl+N Show/hide Plant Viewer navigation bar Ctrl+P Print page in active window Ctrl+F Find Tag F5 Back F6 Forward F7 Next Page 7.
Alarm symbols The following alarm states can be displayed: Alarm state Display Into Alarm (Extended alarm) Into Alarm Indicated by a swinging red alarm bell Acknowledged alarm Indicated by a red alarm bell marked with a tick Indicated by a gray alarm bell marked with a tick Indicated by a gray bell marked with a cross Unreset alarm Normal not reset (Extended alarm) Symbol Indicated by a red alarm bell Maintenance and operating hours events For run-time and maintenance events a clock with a spanne
tion Transient Default value Object is switching status, e.g. from stage 1 to stage 2. Default value is assumed. Automatically The object is in normal state. The priority list can be displayed graphically in output objects as an additional feature telling which priority is currently writing to the output and which values may become active later on. 7.10 Handle alarms in the Plant Viewer Alarms can be acknowledged or reset with the Super Genie.
1. Move the mouse cursor over the alarm bell. Left-click inside the frame to open the super genie. Data point selection. Data point description. Hardware state. Process state. Acknowledge alarm. Reset alarm. Exit button. 2. 3. 4. Click to display data point information. Acknowledge or reset the alarm using the buttons. Exit the super genie. 7.
Example setpoint With write access Without write access Example buttons With write access Access rights Without write access Counters Analog value Digital or multistate value Low Medium High Operation elements Object type Standard buttons for operation Description Process Digital value ON button (green) Click to switch equipment on OFF button (grey) Click to switch equipment off AUTO button Click to set state to automatic MANUAL button Click to set state to manual Option button Click
slide switch Change values with super genie 1. 2. 3. 4. 5. Operate plants Set new value with slider. Click a genie to open the super genie. Use one of the standard buttons described above, to change the value. For analog values, the entered value must be confirmed by pressing the enter key. Check that the new value has been written to and reported from the field, and that the point status has changed to manual. . Click the button to reset point status to automatic Close the super genie.
7.
· Page size Page commands (on entry, on exit and while displayed) · Window tab: · Window title · Parent window · Child window(s) · Window mode · Window position · Window size 7.13 Locate page data Note List object properties for a graphics page You can display a list of objects and their properties on a graphics page. 1. Open the corresponding graphics page. 2. 3. on the navigation bar. Click Page Data Snapshot OR Right-click the graphic page background. The context menu opens.
2. Check the displayed preview, if necessary using the scroll bars or by zooming in and out. Print this preview on the selected printer (Page setup). 3. Note Click Exit Toggle Zoom on the window title bar to close the page preview window. If you are ready to print directly, you can start printing straight from the preview, by clicking the Print button Print graphics page on the Print Preview toolbar. Print present graphics page 1.
7.15 Navigation Navigate to other Desigo Insight programs via object or property name (Send To…) You can navigate to other Desigo Insight programs from Plant Viewer via the object name or property name of the selected symbol. This feature can be used for example 1. To open Alarm Viewer from a graphics page in Plant Viewer in which an alarm is indicated, automatically filtering the list of alarms by the corresponding object name or property name.
Send To Actions · · · View trended series (select from below list) This action allows you to view the trends using the selected trend log in List of trendlog objects.This option is disabled when there are no existing recorded trend series. Start online trend This action allows you to set up an online trend for the object sent. Always start online trend: This option is enabled when you select the Start online trend radio button. Skip this dialog in future and directly start the online trend.
tion. Youmust have “Create object” privileges to view this dialog. · Modify offline trend This action allows you to view Modify trend log dialog box. You can modify some of the properties of trend log object and delete trend log object. For delete operation, you must have delete object privileges while for modify, you must have either create or delete object privileges in System Configurator. Refer the property table in 9.4.9.3 Chapter Settings in the Trend Log Multiple object for some of the properties.
7.16 Exit Plant Viewer Exit the Desigo Insight Plant Viewer as follows: 1. Save workspace configuration Exit the Plant Viewer Right-click anywhere in the Plant Viewer navigation bar (no on a button). Select Exit Plant Viewer. OR Click the Exit button on the right corner of the Plant Viewer navigation bar. OR Left-click in the Plant View navigation bar in the foreground and press . The position of the open graphics pages can be automatically saved when exiting Plant Viewer.
8 Chapter overview This section describes how the Desigo Insight alarm system works, and how you may use it. 8.1 What the alarm system does Alarm handling Principles of alarm handling Your Desigo system controls your building automation and control system plants. Sometimes events occur (e.g. a fault) that is important for the operator to know and requiring user intervention. The alarm system processes and issues the appropriate reports (e.g. to a printer or pager) for such events.
Alarms and events Alarms are actually a specific type of Desigo Insight event. There are four event types: 1. 2. 3. 4. Alarm events. System events. User events. Status events. Events are all things that happen within your Desigo system. They are subdivided into the categories above on the basis of their character. All events are capable of being transmitted to one or more “receivers”. They are all assigned a “priority”, i.e. . a level of importance.
Simple alarm Simple alarms (or alarm objects) do not require you to acknowledge or reset, they simply return to the normal state when the monitored condition (e.g. a dirty filter) returns to normal. Basic alarm More important alarms (e.g. lack of water) must be acknowledged. After the alarm state is eliminated, the plant is once again released after acknowledgement. Extended alarm For an extended alarm (e.g. velocity monitor), the reset returns the plant to normal.
Event priority Like alarms, the other 3 event types also have a priority: the same priority text description (e.g. “High”, “Low” etc.) is used for all four. Also like alarms, "Category" is not used with the other events. Alarm applications A number of applications are employed on the Desigo Insight management station for alarm handling: · Taskbar (Desigo Insight Shell) Shows a summary of all site alarms · Alarm Viewer Shows the state of all alarm objects not in a normal state.
Navigate between alarm applications You can jump between various Desigo Insight applications using principally Send to... as follows: Note that a filter is applied if you use the taskbar to jump to Alarm Viewer. When using the Send to... function, select the object of concern before right clicking to display the option list. 8.
The meanings of the various icons is as follows: Symbol Description Alarm cause User intervention Alarm Acknowledged alarm Acknowledged alarm, not reset. Unacknowledged alarm, not reset. Alarm cause exists. Alarm cause exists. None Acknowledged alarm Alarm cause no longer exists. Acknowledged alarm Alarm cause no longer exists. None No more display Alarm cause no longer Alarm reset. exists.
Manual switch. The Reliability icon means that the signal source has become unreliable, perhaps being open circuit. Operating mode warns if an override has been applied. Taskbar - alarm summary icons These are displayed at the top right hand side of the Desigo Insight taskbar. As described in the section on navigation, you can click one of the three symbols at any time to display the Alarm Viewer. The display for the selected symbol is filtered by alarm priority.
Note When using scopes, the popup window only shows alarms assigned to you. Alarm Router The Desigo Insight Alarm Router forwards all event messages including alarm messages to receiver devices, so-called receivers. The following receivers may be configured for Desigo Insight: · · · · · · Printers. Fax machine. E-mail receiver. Pager receiver. File. Management station pop-up. The routing of event messages can be finely tuned, according to: · Alarm priority.
Pop-up window 1. Alarm Viewer 1. Right-click alarm entry in the Alarm Viewer and Send to > Plant Viewer in the context menu. Log Viewer 1. Check if other alarms have been triggered This is most conveniently done via Alarm Viewer. Start Alarm Viewer and order the “time of alarm” column, so that the most recent alarms are visible. You can jump directly to Plant Viewer by right-clicking the alarm and using Send to.... Alternatively you may display Log Viewer, Alarm tab.
If you make a multiple selection then the interaction symbols are displayed according to states that are common to that selection. If both buttons are grayed out, then there is no common interaction available to your selection. Select alarms that all have the same state to enable a multiple acknowledge or reset. The alarm states are displayed with symbols and text. The symbols are described in the section on Plant Viewer.
8.3.1 Alarm suppression Alarms can temporarily suppressed for commissioning and service work. Such suppressed alarms do not sent alarm messages to the recipients. No messages or only after the fact, for pending alarm, may be sent depending on the suppressed alarms.
8.4 Alarm Viewer: General operation Alarm Viewer displays a list of the states of all alarm objects that are in an abnormal state. You can acknowledge and reset alarms from here. The layout of Alarm Viewer is as follows: The display table can be influenced in the Alarm Viewer. These operations include: · Ordering of columns · Filtering the display · Select which columns are shown in the table These operations are described in detail in the general handling section of this User guide.
Menu bar File Print Print Preview Page Setup Exit Prints the active document. Displays full pages. Opens a dialog box for print settings. Quits the Insight program Alarm Viewer. Edit Find Finds objects matching the specified attributes. System Browser Toolbar Status bar Technical View User View System View Remove Filters Remove Sorting Show Gridlines… Displays / hides the System Browser pane. View Alarm Acknowledg e Reset Refresh Alarms To Do...
Filter You can filter the Alarm Viewer table by the same general methods described in the general handling section. Save present filters Filter Connected Sites Turn off filter Display, whether filter is active List of available filters Actively save filters (if available) The filter effect is also applied if you jump from the Desigo Insight taskbar alarm summary icons.
8.5 General Adjust the alarm handling system You can individually configure alarm response based on your operational requirements with Desigo Insight. For example, you can determine which alarms are sent where, e.g., SMS to the janitor from Friday, 5:00 pm through Monday, 8:00 am.
Router configuration Alarm Routing is engineered using System Configurator and Alarm Router . System Configurator is used in this instance for: · Creating, modifying and deleting Alarm Routing groups · Adding, modifying and deleting Alarm receivers · Configuring which management stations log event messages and which event types Alarm Router is used for: · Enabling and disabling alarm routing to an Alarm receiver · Applying time control to the routing of alarms. · Configuring the alarm pop-up.
8.7 Create an event routing group Alarm configuration with System Configurator Event message groups (including alarm routing groups) are created via System Configurator. You create the group according to: · The event type (Alarm, System, User or Status) · Event priority · Site Start System Configurator , and proceed as shown. 1. 2. Right-click "Router Groups" folder. Select Add. OR Right-click an existing group and select Copy. Right-click and Add OR right-click and Copy General 1. 2. 3. 4.
Route by designation Route by designation groups or classifies alarms by using a portion of the designation chain as a routing criteria. Set up routing after designation After enabling Route after Designation, two decisions must be made. Wildcards (global characters) – Designation type: Select the view (technical view, user view, system view) to complete the designation chain for alarm routing. – User syntax: (wildcards or regular expression). These options determine how the chain criteria are applied.
Global characters allow the user to route all objects belonging to the designation portion Ahu’FanEx. User syntax "regular expression More complex chain comparisons can be created with Regular Expression syntax. Valid syntax is as follows: . x|y [xyz] [^xyz] [a-z] [^a-z] \ ^ $ * + ? {n} {n,} {n,m} \d \D \s \S \w \W corresponds to any individual character. Corresponds to either x or y Character set. Corresponds to any characters listed in the brackets. Negative character set.
In the case of SCADA systems then there are entries, which you may use as criteria for your routing group. Remove You can delete categories with << Remove from the Routed Sites drop-down box. Priorities 1. 2. Select Priorities tab. Select priorities for routing this router group. Events 1. 2. Select the Events tab. Select the events and click Add >>. The selected events are displayed in the Routed categories box. 3. (See Chapter 15, Appendix) Click OK to save the data.
5. Note Example: Click OK. When forming router subgroups (e.g.: Intrusion, intrusion in vault, intrusion ground floor), routing only works when you select the router texts. Routing does not support wildcards. Thus, when you select e.g. Intrusion, only this router group is routed to one receiver. Router text Intrusion Intrusion in vault Intrusion ground floor Selected Yes No No Routing Yes No No Definition in the Object Viewer: , and proceed as shown. Start Object Viewer 1. 2. 3. 4.
The used column displays the number of times the text is assigned to data points. Important: Text routing is accomplished via the Routed Texts list box in the System Configurator and the Text table in the Object Viewer. The routing occurs between the Text table in the Object Viewer to the description for the data point. As a consequence, check that each routing text functions to the outside at least once! Note You can only delete text, when Used = 0. Delete router group 1. 2.
Add a new alarm printer 1. 2. 3. 4. 5. 6. Open the System Configurator in the Desigo Insight taskbar. Click + to expand the browser. Right-click and Add to open the assistants. Create an alarm system. Create an alarm receiver. Link the alarm group with a receiver with the Alarm Router . 1. 2. 3. Open the System Configurator in the Desigo Insight taskbar. Open Desigo Insight Programs > Alarm Router > Alarm Printer by clicking +. Right-click the Alarm Printer folder and select Add.
Notes Before adding a new alarm printer in System Configurator, you must first install the alarm printer in Windows (Start > Settings > New Printers). A single line printer prints alarms line-by-line until the page is full. (A line printer, by contrast, prints alarm messages line by line until the page is full.) In the case of a remote alarm printer we suggest that a special alarm routing group is created to route just urgent alarms to the remote printer. A line printer (e.g.
Define scheme Scheme defines the content of the pop-up. Two schemes are defined by default. Example System 1. Click ADD on the Scheme column to create a new scheme, OR Click Properties scheme to change a selected scheme. 2. Enter a clear designation in the Name field for the pop-up scheme. 125 / 146 Siemens Building Technologies Desigo Insight, Operating the management station, V6.
3. 4. Select desired contents in the Available Fields list. The Available fields use the same descriptors as are visible in Alarm Viewer and Log Viewer (Alarm tab). Click Add >>. 5. 6. 7. 8. 9. 10. 11. Click to change pop-up display sequence. Click Hide Labels to display just the values. Define the display of the buttons in the same way. Click Preview to check the pop-up appearance. Click OK to exit the preview. Click OK to save the scheme. Click OK to save the pop-up window.
Buttons in pop-up Route alarms to a pager Defining a modem group The following table describes buttons available to the Alarm pop-up. They vary depending on the configuration of the pop-up window: Buttons Action Plant Viewer Opens the corresponding plant page in the Plant Viewer. The pop-up remains on top. Alarm Viewer Opens Alarm Viewer (filtered to display all alarms with a pop-up for pending alarms) and is used to reset the pop-up for pending alarms. Silence For switching the audio alarm.
11. Select a modem from the Available modems list. 12. Option: Select the modem in the Selected Modems list and click Configure special settings. You can further modify the configuration. Desigo Insight settings thus override Windows settings (settings not visible in Windows). Click Use Default to reassume Windows settings. 13. Click OK (several times) to save the modem group. Define a pager receiver 3. in the Desigo Insight taskbar.
Note Multiple script files are available adapted to various pager service providers (D1, D2 and E-Plus). It is possible to change these files with a text editor, but the knowledge required to this end is not within the scope of this handbook. Your Siemens representative will be able to assist you here if necessary. Defining a Pager receiver 1. 2. 3. in the Desigo Insight taskbar. Open the System Configurator Open Desigo Insight Programs > Alarm Router > Pager > Pager Receiver by clicking +.
{Value} Value {UnitText} Unit text {SystemDesignation} System designation {UserDesignation} User designation {EventMessage} Event message {ToDoText} Instruction Note Depending on the pager or SMS service, only a limited number of characters may be available for transmission. Thus, send a test message to determine if all characters are transmitted properly. If necessary, you may need to drop some information (e.g. system name) from your message file.
4. Configure the e-mail receiver system. System Name Name, e.g. my_e-mail (applies only to Desigo Insight). Comment Description E-Mail Account Use default account: The Default Mail Account is often set up on a workstation using an e-mail application such as Microsoft Outlook Express. Specify Account…: Configure account in the following dialog box. 5. Option: Click Specify Account. Enter the following: if unsure, contact your e-mail administrator. Tip Server Name The server must support SMPT.
– Open the MS Windows command interpreter (the DOS window in Windows) – Enter NSLOOKUP. – Enter SMTP. Define addresses for the e-mail 6. Click Finish to save the data. 1. 2. 3. Open the System Configurator in the Desigo Insight taskbar. Open Desigo Insight Programs > E-Mail > E-Mail Receiver by clicking +. Right-click the E-Mail Receiver folder and select Add. 4. Configure the e-mail receiver. 5.
The From field contains the e-mail address entered in the Mail Account window (see above). The Subject refers to the subject of the "E-mail receiver” definition, also above. The time stamp refers to the e-mail transaction, not the time of the event. Opening the mail reveals: Alarm message ApolloP 22/08/2002 07:41:37 XxAla’XxC101’XxPer’XxMVal’XxMV001 In Alarm Text Priorität 3 AS101 2 Stufe 1 Apollo:AS101’ XxAla’XxC101’XxPer’XxMVal’XxMV001 Alarming \Controller 101 \Leistung \Gruppe Mehrzustandswert \Me
Delay times can be entered in the Routing Table Trouble shooting e-mail problems . Log Viewer contains a message in the event of both successful and unsuccessful e-mail transmission from the Desigo Insight management station to the SMTP Server: This should be checked first in the case of any problems.
6. Click Next. 7. Configure the settings 8. Pass-through Checkbox selected: Apply the data from the service provider (Do not forget the release 0 for in-house plants). Checkbox is not selected: Dial properties explicitly entered. Country/region code Area code Phone number Entries required if transfer was not selected. Number of retries Number of attempts to send message. Delay times between the individual attempts. Click . The Windows Fax and Scan dialog box opens. 9.
The Fax Management Console is a Windows 7 utility. To modify the fax settings, click Tools>Fax settings…>Next. and in the Fax Client Console select Note The message template determines the contents and format of the alarm message. (For information on how to modify the message template, see “Altering the appearance of messages” in the e-mail section.). The program Microsoft Fax generates a line before the alarm message.
Designation replacement file 5. Click Finish to save the data. 8.8 Alarm Router display Corresponding implementation file. Routing alarms using the Alarm Router Here we show the main Alarm Router view with the routing table displayed. In particular we see that the group “All Alarms” is routed to both a printer (“PRINTER1”) and a pop-up service (“POP-UP-1”). We also note that both routes are enabled.
Priority Repetition Delay Comment Repetition determines when and how often event messages are re-transmitted to the receiver. Delay determines when and how long event messages are delayed transmitted to the receiver. Text field. Receiver table The Receiver table shows possible recipients for event messages. Table column Receiver Description Color Backup Receiver Comment The receiver determines the location and format for issuing event messages. The receiver is defined in the System Configurator (e.g.
5. 6. Route event messages according to a time schedule Select the target receiver type and name. Click OK. The entry appears in the routing table. Normally, event messages (including alarms) are routed continuously to a receiver unless it is “disabled”. Alternatively, routing can be done according to a time schedule, so that, for example, alarms are routed to a security printer outside of working hours, and at other times to a BACS room printer.
4. 5. 6. 7. Define a schedule name, e.g. weekend, and click OK. Select the Weekly Schedule tab. Right-click a weekday. Select Add Period. Configure the period by: · Define receiver data. · Specify start day and time. · Specify end day and time. 8. Click OK. 9. Click Create an exception and then Yes to save the schedule. 1. 2. 3. Select the Overview Exception tab. Right-click the corresponding date. Select Add Period. Configure the period by: · Defining the new receiver. · Defining the start date.
5. Click Assign the Time Schedule to an alarm group 1. 2. 3. and then Yes to save the schedule. Open the Alarm Router in the Desigo Insight taskbar. Select the corresponding row. Right-click in column Receiver / Schedule. Select Select Schedule…. 4. Select Select Routing Group…. 5. Select the desired routing group. 6. Click OK. The changed data is saved.
Disable routing to a receiver Alarms for a router group can be suppressed so that it is not routed to the appropriate receiver. 1. 2. Open the Alarm Router in the Desigo Insight taskbar. To disable the routing to a particular Alarm receiver, simply click the Enable box shown. These messages are lost if additional alarms occur while the receiver is disabled. When the receiver is disabled the messages are stored in a clipboard and routed once the receiver becomes enabled.
1. 2. 3. Select the corresponding row. Right-click the Repetition column. Select Enable repetition. 4. 5. Select the checkbox Enable repetition. Select the checkbox Repeat to-alarm events only as long as the alarm remains unacked. Configure the redial. 6. 7. Configure delay No. Number or redials, e.g. when the line is busy or not available. Only when the alarm is active. Period [hh:mm] Delay times between the individual attempts. Click OK.
1. 2. 3. Select the corresponding row. Right-click the Delay column. Select Enable delay. 4. 5. Select the checkbox Enable delay. Select the checkbox After delay, route to-alarm events only if the alarm is still unacked. Configure Edit delay. 6. Period [hh:mm] 7. Delay time prior to routing the alarm to the receiver. Click OK. Test pager Described under "Routing alarm messages" below.
Test routing of alarm messages It is often useful to check if a new alarm route works, without actually triggering an alarm. This is the purpose of the “User message”. 1. 2. Open the Alarm Router in the Desigo Insight taskbar. Select File > Send user message…. 3. 4. 5. 6. Select the receiver type and name. Select Message. Enter a message in the text field. Click Send. A user message is sent. The test message should be received at the receiver. If not, check the Log Viewer for specific errors.
Siemens Switzerland Ltd Building Technologies Division International Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58-724 24 24 www.siemens.com/buildingtechnologies Siemens Building Technologies Desigo Insight, Operating the management station, V6.