Specifications

CPUs
1-67
PLC S7-300, CPU Specifications CPU 312 IFM to CPU 318-2 DP
A5E00111190-01
Address areas (I/O)
Peripheral address area,
digital/analog
2 KB/2 KB (freely
addressable)
Distributed 2 KB/2 KB
Process image (cannot be
customized)
128/128 bytes
Digital channels max. 16384 (minus 1 byte
diagnostic address per DP
slave)/16384
Centralized max. 1024/1024
Analog channels max. 1024 (minus 1 byte
diagnostic address per DP
slave)/1024
Centralized max. 256/128
Configuration
Rack max. 4
Modules per
Rack
max. 8
Number of DP masters
integral 1
via CP 1
S7 message functions
Simultaneously active
Alarm-S blocks
max. 50
Time
Real-time clock Yes
Backed-up Yes
Accuracy See Section 1.1.6
Operating hours counter 1
Number 0
Value range 0 to 32767 hours
Selectivity 1 hour
Retentive Yes
Clock synchronisation Yes
On PLC Master
On MPI Master/Slave
Testing and commissioning functions
Status/Modify Variables Yes
Variable Inputs, outputs, flags, DBs,
timers, counters
Number
Monitor Variables
Modify Variables
max. 30
max. 14
Force Yes
Variable Inputs, outputs
Number max. 10
Monitor block Yes
Single sequence
Breakpoint
Yes
2
Diagnostic buffer Yes
Number of entries
(non-alterable)
100
Communication functions
PD/OP communication Yes
Global data communication Yes
Number of GD packets
Sender 1
Receiver 1
Size of GD packets max. 22 bytes
Number of which
consistent
8 bytes
S7 basic communication Yes
User data per job max. 76 bytes
Number of which
consistent
32 bytes for X/I_PUT/_GET;
76 bytes for
X_SEND/_RCV
S7 communication Yes (server)
User data per job max. 160 bytes
Number of which
consistent
32 bytes
S7-compatible
communication
Yes (via CP and loadable
FC)
User data per job Dependent on CP
Number of which
consistent
Dependent on CP
Standard communication Yes (via CP and loadable
FC)
User data per job Dependent on CP
Number of which
consistent
Dependent on CP
Number of connection
resources
12 for PD/OP/S7 basic/S7
communication
Reservation for
PD communication
User-definable
Default
max. 11
from 1 to 11
1
OP communication
User-definable
Default
max. 11
from 1 to 11
1
S7 basic
communication
User-definable
Default
max. 8
from 0 to 8
8
Routing connections max. 4