Table 4. Three-Position (Floating) Function Check.
Connection Terminals
Actuator Response
Voltage at Y1
Actuator’s stem extends
Voltage at Y2
Actuator’s stem retracts
No voltage at Y1 and
Y2
Actuator’s stem maintains
the position
After successful completion of the function check, the
actuator is ready for normal operation.
References
Technical Instructions:
155-547
SAV Electronic Valve Actuator
Non-Spring Return, 24 Vac/dc, Proportional Control
155-548
SAV Electronic Valve Actuator
Non-Spring Return, 24 Vac/dc, 3-Position Control
Dimensions
Product
Numbers
A
B
C
C1
C2
D
E
►►
Weight
lbs (kg)
SAV61.00U
SAV81.00U
10.43
(265)
4.88
(124)
5.91
(150)
2.68
(68)
3.23
(82)
3.15
(80)
3.94
(100)
3.94
(100)
7.87
(200)
4.23
(1.92)
With ASK39.1
11.42
(290)
6.06
(154)
11.81
(300)
7.87
(200)
3.94
(100)
4.74
(2.15)