Datasheet

● fuse monitoring
No
● Overvoltage protection monitoring
No
Short circuit
Short-circuit current making capacity (Icm) / for
switch disconnector / at 690 V AC/440 V DC / without
fuse link / rated value / minimum
7.65kA
Connections
Arrangement of electrical connectors / for main
current circuit
Top and bottom
Tightening torque / with screw-type terminals
● minimum
15N·m
● maximum
22N·m
● Type of connectable conductor cross-sections /
for aluminum conductor / stranded / with lug
1x (2.5 ... 95 mm²), 2x (2.5 ... 50 mm²)
● Type of connectable conductor cross-sections /
for copper conductor / stranded / with lug / acc. to
DIN 46234
1x (2.5 ... 95 mm²), 2x (2.5 ... 50 mm²)
● Type of connectable conductor cross-sections /
for copper conductor / stranded / with lug / acc. to
DIN 46235
1x (25 ... 70 mm²), 2x (25 ... 50 mm²)
Type of electrical connection
● for main current circuit
flat connector
Mechanical Design
Height 150mm
Width 190mm
Depth 161.5mm
Mounting position any
Mounting type floor mounting
Mounting type
● front mounting with 4-hole attachment
No
● front mounting with central attachment
No
● rail mounting
No
Net weight 2200g
Environmental conditions
Degree of pollution 3
Ambient temperature
● during operation / minimum
-25°C
● during operation / maximum
70°C
● during storage / minimum
-50°C
● during storage / maximum
80°C
Certificates
Reference code
3KF2316-0LF11 Subject to change without notice
Page 5/
9
03/08/2019 © Copyright Siemens