Datasheet

Solid-State Switching Devices for Resistive Loads
Solid-State Relays
SIRIUS 3RF22 solid-state relays,
three-phase, 45 mm
4/74
Siemens IC 10 · 2011
4
Overview
With its compact design and a width of just 45 mm, which stays
the same even at currents of up to 55 A, the 3RF22 solid-state
relay offers an ultra small footprint. The logical connection
method, with the power infeed from above and load connection
from below, ensures tidy installation in the control cabinet.
Important features:
LED display
Variety of connection methods
Plug-in control connection
Degree of protection IP20
Zero-point switching
Two- or three-phase controlled
Technical specifications
1)
These products were built as Class A devices. The use of these devices in
residential areas could result in lead in radio interference. In this case
these may be required to introduce additional interference suppression
measures.
2)
If two different conductor cross-sections are connected to one clamping
point, both cross-sections must lie in the range specified. If identical cross-
sections are used, this restriction does not apply.
Type 3RF22 ..-1.... 3RF22 ..-2.... 3RF22 ..-3....
Dimensions (W x H x D) mm
45 x 95 x 47 45 x 95 x 47 45 x 95 x 47
General data
Ambient temperature
During operation, derating from 40 °C °C
-25 ... + 60
During storage °C
-55 ... + 80
Installation altitude m
0 ... 1000; > 1000 ask Technical Assistance
Shock resistance acc. to IEC 60068-2-27 g/ms
15/11
Vibration resistance acc. to IEC 60068-2-6 g
2
Degree of protection
IP20
Insulation strength at 50/60 Hz
(main/control circuit to floor)
V rms
4000
Electromagnetic compatibility (EMC)
Emitted interference
- Conducted interference voltage
acc. to IEC 60947-4-3
Class A for industrial applications
1)
Interference immunity
- Electrostatic discharge
acc. to IEC 61000-4-2
(corresponds to degree of severity 3)
kV Contact discharge 4; air discharge 8; behavior criterion 2
- Induced RF fields
acc. to IEC 61000-4-6
MHz 0.15 ... 80; 140 dBµV; behavior criterion 1
- Burst acc. to IEC 61000-4-4 kV
2/5.0 kHz; behavior criterion 2
- Surge acc. to IEC 61000-4-5 kV
Conductor - ground 2; conductor - conductor 1; behavior criterion 2
Connection type
Screw terminals Spring-type terminals Ring terminal lug
connection
Connection, main contacts
Conductor cross-sections
- Solid mm
2
2 x (1.5 ... 2.5)
2)
; 2 x (2.5 ... 6)
2)
2 x (0.5 ... 2.5) --
- Finely stranded with end sleeve mm
2
2 x (1 ... 2.5)
2)
; 2 x (2.5 ... 6)
2)
;
1 x 10
2 x (0.5 ... 1.5) --
- Finely stranded without end sleeve mm
2
-- 2 x (0.5 ... 2.5) --
- Solid or stranded, AWG cables
2 x (AWG 14 ... 10) 2 x (AWG 18 ... 14) --
Stripped length mm
10 10
Terminal screw M4 -- M5
- Tightening torque,
5 ... 6 mm, PZ 2
Nm
2 ... 2.5 2.5 ... 2
lb.in
18 ... 22 18 ... 22
Cable lug
-- --
- According to DIN 46234 5-2.5 ... 5-25
- According to JIS C 2805
R 2-5 ... 14-5
Connection, auxiliary/control contacts
Conductor cross-sections,
with or without end sleeve
mm
AWG
1 x (0.5 ... 2.5), 2 x (0.5 ... 1.0)
20 ... 12
0.5 ... 2.5
20 ... 12
1 x (0.5 ... 2.5), 2 x (0.5 ... 1.0)
20 ... 12
Stripped length mm
7 10 7
Terminal screw
M3 -- M3
- Tightening torque,
3.5, PZ 1
Nm
0.5 ... 0.6 0.5 ... 0.6
lb.in
4.5 ... 5.3 4.5 ... 5.3
W
H
D