Datasheet

Solid-State Switching Devices for Resistive Loads
Solid-State Contactors
SIRIUS 3RF24 solid-state contactors,
three-phase
4/87
Siemens IC 10 · 2011
4
Technical specifications
1)
These products were built as Class A devices. The use of these devices in
residential areas could result in lead in radio interference. In this case
these may be required to introduce additional interference suppression
measures. The versions 3RF24 ..-1AC55 comply with Class B for residen-
tial, business and commercial applications
2)
If two different conductor cross-sections are connected to one clamping
point, both cross-sections must lie in the range specified. If identical cross-
sections are used, this restriction does not apply.
3)
The screw is not included in the scope of supply.
Order No. 3RF24 ..-1.... 3RF24 ..-2.... 3RF24 ..-3....
Dimensions (W x H x D)
See overleaf
General data
Ambient temperature
During operation, derating from 40 °C °C -25 ... +60
During storage °C
-55 ... +80
Installation altitude m
0 ... 1000; derating from 1000
Shock resistance acc. to IEC 60068-2-27 g/ms
15/11
Vibration resistance acc. to IEC 60068-2-6 g
2
Degree of protection
IP20
Insulation strength at 50/60 Hz
(main/control circuit to floor)
V rms
4000
Electromagnetic compatibility (EMC)
Emitted interference acc. to IEC 60947-4-3
- Conducted interference voltage Class A for industrial applications
1)
Interference immunity
- Electrostatic discharge
acc. to IEC 61000-4-2
(corresponds to degree of severity 3)
kV Contact discharge 4; air discharge 8; behavior criterion 2
- Induced RF fields
acc. to IEC 61000-4-6
MHz 0.15 ... 80; 140 dBµV; behavior criterion 1
- Burst acc. to IEC 61000-4-4 kV
2/5.0 kHz; behavior criterion 2
- Surge acc. to IEC 61000-4-5 kV
Conductor - ground 2; conductor - conductor 1; behavior criterion 2
Connection type
Screw terminals Spring-type terminals Ring terminal lug
connection
Connection, main contacts
Conductor cross-section
- Solid mm
2
2 x (1.5 ... 2.5)
2)
; 2 x (2.5 ... 6)
2)
2x (0.5 ... 2.5) --
- Finely stranded with end sleeve mm
2
2 x (1 ... 2.5)
2)
; 2 x (2.5 ... 6)
2)
;
1 x 10
2x (0.5 ... 1.5) --
- Finely stranded without end sleeve mm
2
-- 2x (0.5 ... 2.5) --
- Solid or stranded, AWG cables
2 x (AWG 14 ... 10) 2 x (AWG 18 ... 14) --
Stripped length mm
10 10 --
Terminal screw
M4 -- M5
- Tightening torque Nm
2 ... 2.5 2 ... 2.5
lb.in
18 ... 22 18 ... 22
Cable lug
-- --
- Acc. to DIN 46234 5-2.5 ... 5-25
- Acc. to JIS C 2805
R 2-5 ,,, 14-5
Connection, auxiliary/control contacts
Conductor cross-section mm
AWG
1 x (0.5 ... 2.5), 2 x (0.5 ... 1.0)
AWG 20 ... 12
0.5 ... 2.5
AWG 20 ... 12
1 x (0.5 ... 2.5), 2 x (0.5 ... 1.0)
AWG 20 ... 12
Stripped length mm
7 10 7
Terminal screw
M3 -- M3
- Tightening torque,
3.5 mm, PZ 1
Nm
0.5 ... 0.6 0.5 ... 0.6
lb.in
4.5 ... 5.3 4.5 ... 5.3
Grounding screw
3)
Size (standard screw) M4 M4 M4
Permissible mounting positions
±10°
NSB0_01703
±10°
© Siemens AG 2010