Datasheet

Solid-State Switching Devices for Resistive Loads
3RF29 Function Modules
General data
4/96
Siemens IC 10 · 2011
4
Technical specifications
1)
Note limitations for power controller function modules. These modules
were built as Class A devices. The use of these devices in residential areas
could result in lead in radio interference. In this case these may be
required to introduce additional interference suppression measures.
1)
Versions are independent of the main circuit.
Type 3RF29 ..-0EA.. 3RF29 ..-0FA.. 3RF29 ..-0GA.. 3RF29 ..-0HA.. 3RF29 ..-0JA.. 3RF29 ..-0KA..
Dimensions (W x H x D) mm
22.5 x 84 x 38 22.5 x 102 x 39 45 x 112 x 44 45 x 112 x 44 45 x 112 x 44 45 x 112 x 44
General data
Ambient temperature
During operation, derating from 40 °C °C -25 ... +60
During storage °C
-55 ... +80
Installation altitude m
0 ... 1000; derating from 1000
Shock resistance acc. to IEC 60068-2-27 g/ms
15/11
Vibration resistance acc. to IEC 60068-2-6 g
2
Degree of protection
IP20
Electromagnetic compatibility (EMC)
Emitted interference
- Conducted interference voltage
acc. to IEC 60947-4-3
Class A for industrial applications
1)
- Emitted, high-frequency interference volt-
age acc. to IEC 60947-4-3
Class B for residential, business and commercial applications
Interference immunity
- Electrostatic discharge
acc. to IEC 61000-4-2
(corresponds to degree of severity 3)
kV Contact discharge 4; air discharge 8; behavior criterion 2
- Induced RF fields
acc. to IEC 61000-4-6
MHz
0.15 ... 80; 140 dBμV; behavior criterion 1
- Burst acc. to IEC 61000-4-4
2 kV/5.0 kHz; behavior criterion 2
- Surge acc. to IEC 61000-4-5 kV
Conductor - ground 2; conductor - conductor 1; behavior criterion 2
Connection, auxiliary/control contacts,
screw terminals
Conductor cross-section mm
2
1 x (0.5 ... 2.5), 2 x (0.5 ... 1.0), 1 x (AWG 20 ... 12)
Stripped length mm
7
Terminal screw
M3
Tightening torque Nm
0.5 ... 0.6
lb.in
4.5 ... 5.3
Transformer, feed-through opening
Diameter mm -- 7 17
Type 3RF29 ..-0EA18 3RF29 ..-0FA08 3RF29 ..-0GA.3 3RF29 ..-0GA.6
Main circuit
Rated operational voltage U
e
V AC --
1)
110 ... 230 400 ... 600
Operating range V AC
-- 93.5 ... 253 340 ... 660
Rated frequency Hz
-- 50/60
Rated insulation voltage U
i
V -- 600
Voltage measuring
Measuring range V -- 93.5 ... 253 340 ... 660
Mains voltage, fluctuation
compensation
%
-- 20
Type 3RF29 ..-0HA.3
3RF29 ..-0KA.3
3RF29 ..-0HA.6
3RF29 ..-0KA.6
3RF29 ..-0JA.3 3RF29 ..-0JA.6
Main circuit
Rated operational voltage U
e
V AC 110 ... 230 400 ... 600 110 ... 230 400 ... 600
Operating range V AC
93.5 ... 253 340 ... 660 93.5 ... 253 340 ... 660
Rated frequency Hz
50/60
Rated insulation voltage U
i
V 600
Voltage measuring
Measuring range V 93.5 ... 253 340 ... 660 93.5 ... 253 340 ... 660
Mains voltage, fluctuation
compensation
%
20