Datasheet
● during storage
°C -55...+80
Installation altitude at height above sea level
maximum
m 1000
Vibration resistance acc. to IEC 60068-2-6 2g
Shock resistance acc. to IEC 60068-2-27 15g / 11 ms
Equipment marking acc. to DIN 40719 extended
according to IEC 204-2 acc. to IEC 750
K
Equipment marking acc. to DIN EN 61346-2 Q
Number of NC contacts for auxiliary contacts 0
Number of NO contacts for auxiliary contacts 0
Number of CO contacts for auxiliary contacts 0
Main circuit:
Number of NO contacts for main contacts 1
Number of NC contacts for main contacts 0
Operating current
● at AC-1 at 400 V Rated value
A 88
● at AC-51 Rated value
A 88
Operating current minimum mA 500
Operating voltage at AC
● at 50 Hz Rated value
V 48...600
● at 60 Hz Rated value
V 48...600
Operating range relative to the operating voltage at
AC
● at 50 Hz
V 40...660
● at 60 Hz
V 40...660
Operating frequency Rated value Hz 50...60
Insulation voltage Rated value V 600
Rate of voltage rise at the thyristor for main contacts
maximum permissible
V/µs 1000
Blocking voltage at the thyristor for main contacts
maximum permissible
V 1600
Reverse current of the thyristor mA 10
Derating temperature °C 40
Active power loss total typical W 117
Surge current resistance Rated value A 1150
I2t value maximum A²·s 6600
Control circuit/ Control:
Control supply voltage frequency
● 1 Rated value
Hz 50
● 2 Rated value
Hz 60
Type of voltage of the control supply voltage AC
Control supply voltage 1
● at AC
3RF23 90-3BA26 Changes preserved
Page 2/
5
22.09.2015 © Copyright Siemens AG





