Datasheet

— at 50 Hz Initial rated value
V 110
— at 50 Hz Final rated value
V 230
— at 60 Hz Initial rated value
V 110
— at 60 Hz Final rated value
V 230
Control supply voltage
● at AC
— at 50 Hz Full-scale value for signal<0>
recognition
V 40
— at 60 Hz Full-scale value for signal<0>
recognition
V 40
Symmetrical line frequency tolerance Hz 5
Control current
● at minimum control supply voltage
— at AC
mA 2
● at AC Rated value
mA 15
Installation/ mounting/ dimensions:
Mounting type screw fixing
Mounting type Side-by-side mounting Yes
Design of the thread of the screw for securing the
equipment
M4
Tightening torque of the screw for securing the
equipment
N·m 1.5
Width mm 180
Height mm 200
Depth mm 163
Connections/ Terminals:
Type of electrical connection for main current circuit ring cable connection
Design of the thread of the connection screw for main
contacts
M5
Tightening torque for main contacts with screw-type
terminals
N·m 2...2.5
Type of connectable conductor cross-section for
main contacts
● for JIS cable lug
JIS C 2805 R 2-5, 5,5-5, 8-5, 14-5
Type of connectable conductor cross-section
● for DIN cable lug for main contacts
DIN 46234 -5-2,5, -5-6, -5-10, -5-16, -5-25
● for AWG conductors
— for auxiliary and control contacts
1x (AWG 20 ... 12)
Type of connectable conductor cross-section for
auxiliary and control contacts
● solid
1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²)
● finely stranded
— with core end processing
1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²)
3RF23 90-3BA26 Changes preserved
Page 3/
5