Data Sheet

Operating current of auxiliary contacts at AC-15
● at 24 V
3A
● at 250 V
3A
Operating current of auxiliary contacts at DC-13
● at 24 V
1A
● at 125 V
0.2A
● at 250 V
0.1A
Operating frequency with 3RT2 contactor maximum 50001/h
Contact reliability of auxiliary contacts one incorrect switching operation of 100 million switching
operations (17 V, 5 mA)
Contact rating of auxiliary contacts according to UL R300 / B300
Influence of the surrounding temperature 1% in the whole temperature range to the set runtime
Power supply influence 1% in the whole voltage range to the set runtime
Switching capacity current with inductive load 0.01...3A
Inputs/ Outputs
Product function
● at the relay outputs Switchover delayed/without
delay
No
● non-volatile
No
Electromagnetic compatibility
EMI immunity
● acc. to IEC 61812-1
EN 61000-6-2
Conducted interference
● due to burst acc. to IEC 61000-4-4
2 kV network connection / 1 kV control connection
● due to conductor-earth surge acc. to IEC
61000-4-5
2 kV
● due to conductor-conductor surge acc. to IEC
61000-4-5
1 kV
Field-bound parasitic coupling acc. to IEC 61000-4-3 10 V/m
Electrostatic discharge acc. to IEC 61000-4-2 4 kV contact discharge / 8 kV air discharge
Safety related data
Protection against electrical shock finger-safe
Type of insulation Basic insulation
Category acc. to EN 954-1 none
Connections/ Terminals
Product function
● removable terminal for auxiliary and control
circuit
Yes
Type of electrical connection
● for auxiliary and control current circuit
screw-type terminals
Type of connectable conductor cross-sections
● solid
1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
3RP2560-1SW30 Subject to change without notice
Page 4/
8
09/12/2019 © Copyright Siemens