Data Sheet

Operating frequency maximum 720001/h
Switching behavior monostable
Mechanical service life (switching cycles)
● typical
10000000
Electrical endurance (switching cycles)
● at AC-15 at 230 V typical
100000
Thermal current 6A
Reference code acc. to DIN EN 81346-2 K
Reference code acc. to DIN EN 61346-2 K
Control circuit/ Control
Control supply voltage at AC
● at 50 Hz rated value
24V
● at 60 Hz rated value
24V
Control supply voltage frequency
● 1 rated value
50Hz
● 2 rated value
60Hz
Control supply voltage at DC
● rated value
24V
Operating range factor control supply voltage rated
value at DC
● initial value
0.8
● Full-scale value
1.25
Operating range factor control supply voltage rated
value at AC at 50 Hz
● initial value
0.8
● Full-scale value
1.25
Operating range factor control supply voltage rated
value at AC at 60 Hz
● initial value
0.8
● Full-scale value
1.25
Switch-on delay time
● at AC maximum
12ms
● at DC maximum
12ms
Off-delay time 14ms
Closing delay
● at AC
12ms
● at DC
6ms
Opening delay
● at AC
14ms
● at DC
13ms
Design of the relay operating mechanism poled
Product component Plug-in socket No
3RQ3018-2AB01 Subject to change without notice