Data Sheet

Contact reliability of auxiliary contacts one incorrect switching operation of 100 million switching
operations (17 V, 5 mA)
Main circuit
Type of voltage DC
Inputs/ Outputs
Property of the output Short-circuit proof No
Outputs
Ampacity of the output relay at AC-15
● at 250 V at 50/60 Hz
3A
Ampacity of the output relay at DC-13
● at 24 V
1A
● at 125 V
0.2A
● at 250 V
0.1A
Electromagnetic compatibility
EMC emitted interference
● acc. to IEC 60947-1
ambience A (industrial sector)
EMI immunity
● acc. to IEC 60947-1
corresponds to degree of severity 3
Conducted interference
● due to burst acc. to IEC 61000-4-4
2 kV
● due to conductor-earth surge acc. to IEC
61000-4-5
2 kV
● due to conductor-conductor surge acc. to IEC
61000-4-5
1 kV
Field-bound parasitic coupling acc. to IEC 61000-4-3 10 V/m
Electrostatic discharge acc. to IEC 61000-4-2 6 kV contact discharge / 8 kV air discharge
Display
Display version
● as status display by LED
LED green
Connections/ Terminals
Product function
● removable terminal
No
Type of electrical connection
● for auxiliary and control current circuit
PUSH-IN connection (spring-loaded connection)
Wire length
● at DC maximum
1000m
Type of connectable conductor cross-sections
● solid
1x (0.25 ... 2.5 mm²)
● finely stranded with core end processing
1x (0.25 ... 1.5 mm²)
● finely stranded without core end processing
1x (0.25 ... 2.5 mm²)
3RQ3018-2AN08-0AA0 Subject to change without notice
Page 3/
7