Datasheet
Power Contactors for Switching Motors
SIRIUS 3RT10 contactors,
3-pole, 3 ... 250 kW
3/12
Siemens IC 10 AO · 2013
3
Contactors with solid-state operating mechanism
The solenoid coil is supplied selectively with the power required
for reliable switching and holding by upstream control electron-
ics.
• Wide voltage range for the control supply voltage U
s
:
Compared with the conventional operating mechanism, the
solid-state operating mechanism covers an even broader
range of control supply voltages used worldwide within one
coil variant. For example, the coil for 200 to 277 V AC/DC (U
s
min
to U
s max
) covers the voltages 200-208-220-230-240-254-
277 V used worldwide.
• Extended operating range 0.7 to 1.25 x U
s
:
The wide range for the rated control supply voltage and the
additionally allowed coil operating range of 0.8 x U
s min
to 1.1
x U
s max
results in an extended coil operating range of at least
0.7 to 1.25 x U
s
, within which the contactors will operate reli-
ably, for the most common control supply voltages of 24, 110
and 230 V.
• Bridging temporary voltage dips:
Control voltage failures dipping to 0 V (at A1/A2) are bridged
for up to approx. 25 ms to avoid unintentional tripping.
• Defined ON and OFF thresholds:
For voltages above 0.8 x U
s min
the electronics will reliably
switch the contactor ON, and for voltages below the value 0.5
x U
s min
it is reliably switched OFF. The hysteresis in the switch-
ing thresholds prevents the main contacts from chattering as
well as increased wear or welding when operated in weak, un-
stable networks. This also prevents thermal overloading of the
contactor coil if the voltage applied is too low (contactor does
not close properly and is continuously operated with overexci-
tation).
• Low control power consumption when closing and in the
closed state.
Electromagnetic compatibility (EMC)
The contactors with solid-state operating mechanism conform to
the requirements for operation in industrial plants:
• Interference immunity
- Burst (IEC 61000-4-4): 4 kV
- Surge (IEC 61000-4-5): 4 kV
- Electrostatic discharge, ESD (IEC 61000-4-2): 8/15 kV
- Electromagnetic field (IEC 61000-4-3): 10 V/m
• Emitted interference
- Limit value class A according to EN 55011
Note:
In connection with converters, the control cables must be routed
separately from the load cables to the converter.
Indication of remaining lifetime (RLT) remaining life time)
Main contactor contacts are working parts which therefore must
be replaced in good time when the end of their service life has
been reached. The degree of contact erosion and thus the elec-
trical endurance (= number of operating cycles) depends on the
loading, utilization category, operating mode, etc. Up to now,
routine checks/visual inspections by the maintenance personnel
were needed in order to gain an insight into the state of the main
contacts.
The remaining lifetime indication function now takes over this
task. It does not count the number of operating cycles – which
does not provide information about contact erosion – but instead
electronically identifies, evaluates and stores the actual prog-
ress of erosion of each one of the three main contacts, and out-
puts a warning when specified limits are reached. The stored
data are not lost even if the control supply voltage for A1/A2 fails.
After replacement of the main contacts, measurement the re-
maining lifetime must be reset using the "RESET" button (hold
down RESET button for about 2 seconds using a pen or similar
tool).
Advantages:
• Additional visual display of various levels of erosion by means
of LEDs on the laterally mounted solid-state module when re-
maining lifetime is 60 % (green), 40 % (orange) and 20 %
(red).
• Early warning to replace contacts
• Optimum utilization of contact material
• Visual inspection of the condition of contacts no longer neces-
sary
• Reduction of ongoing operating costs
• Optimum planning of maintenance measures
• Avoidance of unforeseen plant downtimes
Version 3RT1. . .-.N: for 24 V DC PLC output
2 control options:
7 Control without a coupling link directly through a 24 V DC/≥ 30
mA PLC output (IEC 61131-2). Connection by means of 2-pole
plug-in connection. The screwless spring-type connection is
part of the scope of supply. The control supply voltage which
supplies the solenoid operating mechanism must be con-
nected to A1/A2.
Note:
Before start-up, the slide switch for PLC operation must be
moved to the "PLC ON" position (setting ex works: "PLC OFF").
7 Conventional control by applying the control supply voltage at
A1/A2 through a switching contact.
Note:
The slide switch must be in the "PLC OFF" position
(= setting ex works).
RLT
Reset
60 %
40 %
20 %
60 %
RLT
Reset
60 %
40 %
20 %
40 %
RLT
Reset
60 %
40 %
20 %
20 %
RLT
Reset
60 %
40 %
20 %
NSB0_01150a
LED-
Displays
green
green
red
orange
new
24 V DC
24 V DC/30 mA
PLC output
2
Plug-in connection, 2-pole
3
Shutdown in an emergency
(EMERGENCY-STOP) – optional
Slide switch, must be in
position PLC "ON"
1
ONOFF
PLC
A2A1
L1/L+
NSB0_01143e
3
2
1
N/L-
24 V DC
Slide switch, must be in
position PLC "OFF"
1
Shutdown in an emergency
(EMERGENCY-STOP) – optional
2
NSB0_01144e
2
1
ONOFF
PLC
A2A1
N/L-
L1/L+
© Siemens AG 2012