Data Sheet

Operating power for approx. 200000 operating cycles
at AC-4
● at 400 V rated value
66kW
● at 690 V rated value
102kW
Thermal short-time current limited to 10 s 2400A
No-load switching frequency
● at AC
20001/h
● at DC
20001/h
Operating frequency
● at AC-1 maximum
8001/h
● at AC-2 maximum
3001/h
● at AC-3 maximum
7001/h
● at AC-4 maximum
1301/h
Control circuit/ Control
Type of voltage of the control supply voltage AC/DC
Control supply voltage at AC
● at 50 Hz rated value
23...26V
● at 60 Hz rated value
23...26V
Control supply voltage at DC
● rated value
23...26V
Operating range factor control supply voltage rated
value of magnet coil at DC
● initial value
0.8
● Full-scale value
1.1
Operating range factor control supply voltage rated
value of magnet coil at AC
● at 50 Hz
0.8...1.1
● at 60 Hz
0.8...1.1
Design of the surge suppressor with varistor
Apparent pick-up power of magnet coil at AC
● at 50 Hz
590V·A
Inductive power factor with closing power of the coil
● at 50 Hz
0.9
Apparent holding power of magnet coil at AC
● at 50 Hz
6.7V·A
Inductive power factor with the holding power of the
coil
● at 50 Hz
0.9
Closing power of magnet coil at DC 650W
Holding power of magnet coil at DC 7.4W
Closing delay
● at AC
30...95ms
3RT1065-6AB36-3PA0 Subject to change without notice
Page 5/
11
09/11/2019 © Copyright Siemens