Data Sheet

● at DC
30...95ms
Opening delay
● at AC
40...80ms
● at DC
40...80ms
Arcing time 10...15ms
Control version of the switch operating mechanism Standard A1 - A2
Auxiliary circuit
Number of NC contacts for auxiliary contacts
● instantaneous contact
2
Number of NO contacts for auxiliary contacts
● instantaneous contact
2
Operating current at AC-12 maximum 10A
Operating current at AC-15
● at 230 V rated value
6A
● at 400 V rated value
3A
● at 500 V rated value
2A
● at 690 V rated value
1A
Operating current at DC-12
● at 24 V rated value
10A
● at 48 V rated value
6A
● at 60 V rated value
6A
● at 110 V rated value
3A
● at 125 V rated value
2A
● at 220 V rated value
1A
● at 600 V rated value
0.15A
Operating current at DC-13
● at 24 V rated value
10A
● at 48 V rated value
2A
● at 60 V rated value
2A
● at 110 V rated value
1A
● at 125 V rated value
0.9A
● at 220 V rated value
0.3A
● at 600 V rated value
0.1A
Contact reliability of auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings
Full-load current (FLA) for three-phase AC motor
● at 480 V rated value
240A
● at 600 V rated value
242A
Yielded mechanical performance [hp]
● for three-phase AC motor
— at 200/208 V rated value
75hp
3RT1065-6AB36-3PA0 Subject to change without notice
Page 6/
11
09/11/2019 © Copyright Siemens