Data Sheet

— at 220/230 V rated value
100hp
— at 460/480 V rated value
200hp
— at 575/600 V rated value
250hp
Contact rating of auxiliary contacts according to UL A600 / Q600
Short-circuit protection
Design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required
gG: 500 A (690 V, 100 kA)
— with type of assignment 2 required
gG: 400 A (690 V, 100 kA), aM: 315 A (690 V, 50 kA), BS88: 400
A (415 V, 50 kA)
● for short-circuit protection of the auxiliary switch
required
gG: 10 A (500 V, 1 kA)
Installation/ mounting/ dimensions
Mounting position with vertical mounting surface +/-90° rotatable, with vertical
mounting surface +/- 22.5° tiltable to the front and back
Mounting type screw fixing
● Side-by-side mounting
Yes
Height 210mm
Width 145mm
Depth 202mm
Required spacing
● with side-by-side mounting
— forwards
20mm
— upwards
10mm
— downwards
10mm
— at the side
0mm
● for grounded parts
— forwards
20mm
— upwards
10mm
— at the side
10mm
— downwards
10mm
● for live parts
— forwards
20mm
— upwards
10mm
— downwards
10mm
— at the side
10mm
Connections/ Terminals
Type of electrical connection
● for main current circuit
Connection bar
● for auxiliary and control current circuit
screw-type terminals
● at contactor for auxiliary contacts
Screw-type terminals
3RT1065-6AB36-3PA0 Subject to change without notice