Data Sheet
● instantaneous contact
2
Operating current at AC-12 maximum 10A
Operating current at AC-15
● at 230 V rated value
6A
● at 400 V rated value
3A
● at 500 V rated value
2A
● at 690 V rated value
1A
Operating current at DC-13
● at 24 V rated value
10A
● at 48 V rated value
2A
● at 60 V rated value
2A
● at 110 V rated value
1A
● at 125 V rated value
0.9A
● at 220 V rated value
0.3A
● at 600 V rated value
0.1A
Design of the miniature circuit breaker
● for short-circuit protection of the auxiliary switch
required
gG: 10 A (230 V, 400 A)
Contact reliability of auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)
Short-circuit protection
Product function Short circuit protection No
Design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required
gG: 355 A (690 V, 100 kA)
— with type of assignment 2 required
gR: 350 A (690 V, 100 kA)
● for short-circuit protection of the auxiliary switch
required
gG: 10 A (500 V, 1 kA)
Installation/ mounting/ dimensions
Mounting position with vertical mounting surface +/-90° rotatable, with vertical
mounting surface +/- 22.5° tiltable to the front and back
Mounting type screw fixing
● Side-by-side mounting
Yes
Height 172mm
Width 120mm
Depth 170mm
Required spacing
● with side-by-side mounting
— forwards
20mm
— upwards
10mm
— downwards
10mm
— at the side
0mm
● for grounded parts
3RT1456-2AP36 Subject to change without notice
Page 4/
8
09/12/2019 © Copyright Siemens