Data Sheet

Control circuit/ Control
Type of voltage AC/DC
Type of voltage of the control supply voltage AC/DC
Control supply voltage at AC
● at 50 Hz rated value
96...127V
● at 60 Hz rated value
96...127V
Control supply voltage at DC
● rated value
96...127V
Type of PLC-control input acc. to IEC 60947-1 Type 2
Consumed current at PLC-control input acc. to IEC
60947-1 maximum
20mA
Operating range factor control supply voltage rated
value of magnet coil at DC
● initial value
0.8
● Full-scale value
1.1
Operating range factor control supply voltage rated
value of magnet coil at AC
● at 50 Hz
0.8...1.1
● at 60 Hz
0.8...1.1
Design of the surge suppressor with varistor
Apparent pick-up power of magnet coil at AC
● at 50 Hz
750V·A
Inductive power factor with closing power of the coil
● at 50 Hz
0.8
Apparent holding power of magnet coil at AC
● at 50 Hz
7V·A
Inductive power factor with the holding power of the
coil
● at 50 Hz
0.8
Closing power of magnet coil at DC 800W
Holding power of magnet coil at DC 3.6W
Closing delay
● at AC
60...90ms
● at DC
60...90ms
Opening delay
● at AC
80...100ms
● at DC
80...100ms
Arcing time 10...15ms
Control version of the switch operating mechanism PLC-IN or Standard A1 - A2 (adjustable)
Auxiliary circuit
Number of NC contacts for auxiliary contacts 2
● attachable
4
3RT1476-6PF35 Subject to change without notice
Page 3/
8