Data Sheet

— downwards
10mm
— at the side
0mm
● for grounded parts
— forwards
20mm
— upwards
10mm
— at the side
10mm
— downwards
10mm
● for live parts
— forwards
20mm
— upwards
10mm
— downwards
10mm
— at the side
10mm
Connections/ Terminals
Type of electrical connection
● for main current circuit
Connection bar
● for auxiliary and control current circuit
screw-type terminals
● at contactor for auxiliary contacts
Screw-type terminals
● of magnet coil
Screw-type terminals
Type of connectable conductor cross-sections
● at AWG conductors for main contacts
2/0 ... 500 kcmil
Connectable conductor cross-section for main
contacts
● single or multi-stranded
70...240mm²
● stranded
70...240mm²
Connectable conductor cross-section for auxiliary
contacts
● single or multi-stranded
0.5...4mm²
● finely stranded with core end processing
0.5...2.5mm²
Type of connectable conductor cross-sections
● for auxiliary contacts
— solid
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
— single or multi-stranded
2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG conductors for auxiliary contacts
2x (20 ... 16), 2x (18 ... 14), 1x 12
Safety related data
Product function
● Mirror contact acc. to IEC 60947-4-1
Yes
● positively driven operation acc. to IEC 60947-5-
1
No
Protection against electrical shock finger-safe when touched vertically from front acc. to IEC 60529
Certificates/ approvals
3RT1476-6PF35 Subject to change without notice
Page 5/
8
09/13/2019 © Copyright Siemens