Datasheet

— upwards
10mm
— downwards
10mm
— at the side
6mm
Connections/Terminals
Type of electrical connection
● for main current circuit
spring-loaded terminals
● for auxiliary and control current circuit
spring-loaded terminals
Type of connectable conductor cross-sections
● for main contacts
— solid
2x (0.5 ... 4 mm²)
— single or multi-stranded
2x (0,5 ... 4 mm²)
— finely stranded with core end processing
2x (0.5 ... 2.5 mm²)
— finely stranded without core end
processing
2x (0.5 ... 2.5 mm²)
● at AWG conductors for main contacts
2x (20 ... 12)
Connectable conductor cross-section for main
contacts
● solid
0.5...4mm²
● stranded
0.5...4mm²
● finely stranded with core end processing
0.5...2.5mm²
● finely stranded without core end processing
0.5...2.5mm²
Connectable conductor cross-section for auxiliary
contacts
● single or multi-stranded
0.5...4mm²
● finely stranded with core end processing
0.5...2.5mm²
● finely stranded without core end processing
0.5...2.5mm²
Type of connectable conductor cross-sections
● for auxiliary contacts
— single or multi-stranded
2x (0,5 ... 4 mm²)
— finely stranded with core end processing
2x (0.5 ... 2.5 mm²)
— finely stranded without core end
processing
2x (0.5 ... 2.5 mm²)
● at AWG conductors for auxiliary contacts
2x (20 ... 12)
AWG number as coded connectable conductor cross
section
● for main contacts
20...12
● for auxiliary contacts
20...12
Safety related data
B10 value
● with high demand rate acc. to SN 31920
1000000
Proportion of dangerous failures
● with low demand rate acc. to SN 31920
40%
3RT2015-2JB41 Subject to change without notice
Page 7/
11
05/08/2019 © Copyright Siemens