Data Sheet

Shock resistance with sine pulse
● at AC
10,5g / 5 ms, 6,6g / 10 ms
Mechanical service life (switching cycles)
● of contactor typical
30000000
● of the contactor with added electronics-
compatible auxiliary switch block typical
5000000
● of the contactor with added auxiliary switch
block typical
10000000
Reference code acc. to DIN 40719 extended
according to IEC 204-2 acc. to IEC 750
K
Reference code acc. to DIN EN 81346-2 Q
Ambient conditions
Installation altitude at height above sea level
● maximum
2000m
Ambient temperature
● during operation
-25...+60°C
● during storage
-55...+80°C
Main circuit
Number of poles for main current circuit 3
Number of NO contacts for main contacts 3
Operating voltage
● at AC-3 rated value maximum
690V
Operating current
● at AC-1 at 400 V
— at ambient temperature 40 °C rated value
18A
● at AC-1
— up to 690 V at ambient temperature 40 °C
rated value
18A
— up to 690 V at ambient temperature 60 °C
rated value
16A
● at AC-2 at 400 V rated value
7A
● at AC-3
— at 400 V rated value
7A
— at 500 V rated value
6A
— at 690 V rated value
4.9A
● at AC-4 at 400 V rated value
6.5A
● at AC-5a up to 690 V rated value
15.8A
● at AC-5b up to 400 V rated value
5.8A
● at AC-6a
— up to 230 V for current peak value n=20
rated value
4A
3RT2015-1AV01 Subject to change without notice
Page 2/
12
09/11/2019 © Copyright Siemens