Data Sheet

— up to 400 V for current peak value n=20
rated value
4A
— up to 500 V for current peak value n=20
rated value
3.8A
— up to 690 V for current peak value n=20
rated value
3.6A
● at AC-6a
— up to 230 V for current peak value n=30
rated value
2.7A
— up to 400 V for current peak value n=30
rated value
2.7A
— up to 500 V for current peak value n=30
rated value
2.5A
— up to 690 V for current peak value n=30
rated value
2.4A
Minimum cross-section in main circuit
● at maximum AC-1 rated value
2.5mm²
Operating current for approx. 200000 operating
cycles at AC-4
● at 400 V rated value
2.6A
● at 690 V rated value
1.8A
Operating current
● at 1 current path at DC-1
— at 24 V rated value
15A
— at 110 V rated value
1.5A
— at 220 V rated value
0.6A
— at 440 V rated value
0.42A
— at 600 V rated value
0.42A
● with 2 current paths in series at DC-1
— at 24 V rated value
15A
— at 110 V rated value
8.4A
— at 220 V rated value
1.2A
— at 440 V rated value
0.6A
— at 600 V rated value
0.5A
● with 3 current paths in series at DC-1
— at 24 V rated value
15A
— at 110 V rated value
15A
— at 220 V rated value
15A
— at 440 V rated value
0.9A
— at 600 V rated value
0.7A
Operating current
● at 1 current path at DC-3 at DC-5
— at 24 V rated value
15A
3RT2015-1AV01 Subject to change without notice
Page 3/
12
09/11/2019 © Copyright Siemens